MINIPLEX Transponder Product Selection
Transponder Type
Model
Description
Basic Transponder, includes bay equipment with power distribution interface, and 4100-0620 Basic
4100-9600
Transponder Interface Module mounted in Block A
Local Mode Transponder, includes bay equipment with power distribution interface, and
4100-9601
4100-0625 Local Mode Transponder Interface Module mounted in Block A
Local Mode Controller Selection
Model
Description
4601-9108
Flush mount
4601-9109
Surface mount
4601-9110
Flush mount
4601-9111
Surface mount
Communication Modules
Model
Description
4100-6031
Select one per
4100-6032
EPS+ or EPS
4100-6033
4100-6038
Dual RS-232 Interface
4100-6045
Decoder Module
4100-6048
VESDA Aspiration System Interface
4100-9816
Master Clock Interface Module with one standard RS-232 port (see S4100-0033)
Enhanced and Expansion Power Supplies and Accessories
Model
Voltage/Listing
4100-5311
120 VAC
4100-5313
220-240 VAC
4100-5325
120 VAC
4100-5327
220-240 VAC
Dual Class A IDNAC Isolator (DCAI), converts a single Class B IDNAC SLC input to two
Class A or two Class B SLC outputs; provides short circuit isolation between each Class A
or B output circuit; connect up to two DCAI modules per IDNAC SLC input up to a
4100-6103
maximum of 6 DCAI modules per EPS; each isolated output SLC used requires one IDNAC
address; the total current remains controlled by the Class B input source SLC at 3 A
maximum
Model
Voltage/Listing
4100-5101
120 VAC
4100-5103
120 VAC, Canadian
4100-5102
220-240 VAC
4100-5115
NAC Expansion Module, 3 NACs, Class A/B, mounts on XPS only
4100-5152
12 VDC Power Option, 2 A maximum
4100-0636
Box Interconnection Harness Kit (non-audio); order one for each close-nippled cabinet
Miscellaneous Options and Accessories
Model
Description
24 Point I/O Module for external connections, select each point as either a switch input (momentary or maintained) or an
4100-1290
output (for lamp/LED/relay); requires 1 Slot (refer to data sheet S4100-0032 for additional information)
4100-0632
Terminal Block Utility Module with 2, 16 position terminal blocks on 4" x 5" single block, for of up to 12 AWG wire (3.31 mm
4100-0633
Door Tamper Switch, connects into Transponder Interface Module, one per cabinet assembly if required
4100-0634
120 VAC
4100-0635
220/230/240 VAC
4100-9837
Green LED Power-on Indicator Kit, required for ULC listing of MINIPLEX transponder; mounts on solid door knockout
Series resistor for WSO, IDCs (N.O. water flow and tamper on same circuit, wires after water flow and before tamper) 470 Ω,
2081-9031
1 W, encapsulated, two 18 AWG leads (0.82 mm
* Standard power supply NACs can provide synchronized strobe or SmartSync, two-wire operation.
Red with white
Local Mode Controller, 3-gang plate mounted;
lettering
flush mount requires a 1 ½" (38 mm) deep
3-gang box; surface mount controllers include a
Beige with black
matching mounting box; see p. 7 for details
lettering
City Circuit, with disconnect switches
City Circuit, without disconnect switches
Alarm Relay, 3 Form C relays, 2 A @ 32 VDC
Description
UL &
Enhanced Power Supply (EPS+); 9 A Enhanced Power
ULC
Supply/battery charger with 250 point IDNet 1+ interface,
3 Class B IDNAC SLCs, RUI+ isolated output communications
interface, and auxiliary relay; 120 VAC model has selectable
UL
low battery cutout
UL &
Enhanced Power Supply (EPS); 9 A Enhanced Power
ULC
Supply/battery charger with 3 Class B IDNAC SLCs, RUI+
isolated output communications interface, and auxiliary relay;
UL
120 VAC model has selectable low battery cutout
Description
Expansion Power Supply (XPS); 9 A output, 3 built-in
UL
Class A/B NACs, rated 3 A for Special Application
ULC
appliances (2 A for Regulated DC); NACs can be selected
as auxiliary power outputs, derated to 2 A for continuous
UL
duty, total per XPS is 5 A; 4100-5103 has low battery cutout
Power Distribution Module (PDM) select per system voltage; one required per box
(see specification details on page 6)
2
), 2 ½" L x 1 ⅜" W x 1" H (64 mm x 35 mm x 25 mm)
4
Supv.
Alarm
87 mA
87 mA
normal
87 mA
87 mA
in local mode
112 mA
112 mA
Supv.
Alarm
normal
12 mA
12 mA
in local mode
20 mA
60 mA
Size
Supv.
Alarm
N.A.
20 mA
36 mA
N.A.
20 mA
36 mA
N.A.
15 mA
37 mA
1 Slot
132 mA
132 mA
3 Slots
85 mA
163 mA
1 Slot
132 mA
132 mA
1 Slot
132 mA
132 mA
Size
Supv.
Alarm
217 mA
480 mA
4 Blocks
Right
with 200 IDNet
Side
devices and 20
device LEDs in alarm
4 Blocks
Right
125 mA
220 mA
Side
1 Block
6.5 mA
6.5 mA
Size
Supv.
Alarm
2 Blocks
50 mA
50 mA
N.A.
25 mA
25 mA
1 Block
1.5 A maximum