The following module type codes, which have special releasing functions, can be programmed into the control
panel. Special releasing device type codes are listed below.
"ABORT SWITCH" – A type code assigned to an MMX Monitor Module which performs the abort functions
described above. The MMX is connected to a UL-listed abort station such as the Notifier ARA-10. All wiring
is fully supervised, following the wiring instructions for the MMX modules described earlier in this document.
Multiple Abort Switch modules may be installed and they will provide a logical "OR" function, similar to
multiple conventional abort switches on a single conventional zone.
"MAN. RELEASE" – A type code assigned to an MMX Monitor Module which performs a manual release
function. The MMX is connected to a UL-listed manual station such as the Notifier ARA-10 or NBG-10. It will
override all Abort Switch modules that are active and programmed to the same releasing zone. All wiring is
fully supervised, following the wiring instructions for the MMX modules described earlier in this document.
Multiple MAN. RELEASE modules may be installed, and they will provide a logical "OR" function, similar to
multiple conventional release switches on a single conventional zone.
"REL CKT ULC" – A type code assigned to a CMX control module, or one of the four Notification Appliance
Circuits on the control panel, which activates a releasing solenoid or other releasing device. All wiring to the
release device, and the release device itself, is fully supervised and suitable for use with limited energy cable.
The release device activates when an initiating device programmed to the same zone activates (two devices if
cross-zoning selected); and the delay timer (if used) expires; and no Abort Switch (if used) is active. You can
program multiple Release CKT types to the same releasing zone, and they all activate when the zone becomes
active.
"RELEASE CKT" – This type code operates similar to "REL CKT ULC" but the release device circuit is
supervised for open circuits and ground faults only (not short circuits). You cannot use this type code for
applications requiring ULC Listing or with limited energy cable.
Do not use REL-4.7K (panel output) or REL-47K (CMX module) with this type code.