The control panel is designed for use in commercial, industrial, and institutional applications and meets the
requirements for service under the National Fire Protection Association (NFPA) Standards outlined in this
Appendix. The minimum system components required for compliance with the appropriate NFPA standard are
listed below.
AFP-200 Control Panel containing the main circuit board, cabinet (backbox and door), main supply trans-
former and power supply.
Batteries (refer to Appendix A for standby power requirements).
Initiating Devices connected to one of the control panel's initiating device circuits.
Notification Appliances connected to the control panel's Notification Appliance Circuit or via a CMX mod-
ule.
The following additional equipment is needed for compliance with the NFPA standards listed below:
NFPA 72-1993 Central Station Fire Alarm Systems (Protected Premises Unit)
UDACT Universal Digital Alarm Communicator/Transmitter or Notifier 911ACDACT for connection to a
compatible UL-listed Central Station DACR or Protected Premises Receiving Unit. This unit must be in-
stalled as outlined in Figure B-1.
NFPA 72-1993 Auxiliary Fire Alarm System
RTM-8 Relay Transmitter Module or 4XTM Transmitter Module for connection to a compatible UL-listed
Local Energy Municipal Box. This unit must be installed as outlined in Figure B-3.
NFPA 72-1993 Remote Station Fire Alarm System
RTM-8 Relay Transmitter Module or 4XTM Transmitter Module for connection to the Fire•Lite RS82 Re-
mote Station Receiver. See Figure B-5 for installation instructions for this unit
UDACT Universal Digital Alarm Communicator/Transmitter or Notifier 911AC DACT for connection to a
compatible UL-listed remote station DACR. This unit must be installed as outlined in Figure B-1 and B-2.
NFPA 72-1993 Proprietary Fire Alarm System
Notifier NIB-96 Network Interface Board. See Figure B-6 for installation instructions for this unit. The
NIB-96 must be installed in the receiving system (AM2020/AFP1010). For more information on the NIB-96,
refer to the NIB-96 Manual, Document 15666
AFP-200 Instruction
PN 15511:F2
OR
10/11/99
77