Notifier AFP-200 Instruction Manual page 16

Intelligent fire detection and alarm system
Hide thumbs Also See for AFP-200:
Table of Contents

Advertisement

This section contains brief descriptions of annunciators that can be used with the AFP-200. For detailed
information, refer to Appendix C and appropriate annunciator manuals for detailed wiring requirements.
The Annunciator Control Module-
16AT or AFM-16AT contains 16
red alarm and 16 yellow trouble
LEDs, a system trouble LED, an
ON LINE/POWER LED, and a
local piezo sounder with switches
for control panel ACKNOWL-
EDGE, SILENCE, RESET, and
DRILL. The AFM-16AT is fixed at
address "1," and will not accept
expanders.
The Annunciator Expander Module-
16AT expands the ACM-16AT by 16
system points. The ACM-16AT supports up to
three expanders, providing a maximum of 64 points
of annunciation.
The Annunciator Fixed Module-16A is intended for
use in systems that require 16 annunciation points
or less. Multiple annunciators may be used by
setting all annunciators to Receive Only, except the
last AFM-16A in line. Each annunciator's address
is internally fixed at "1."
The LDM-32 Lamp Driver Annunciator Module provides 32 alarm lamp
driver outputs for connection to a custom graphic annunciator. The LDM-32
can be alternately selected via a DIP switch for 16 alarm, 16 trouble, and 16
switch inputs for control of such system functions as signal silence and system
reset.
The Lamp Driver Annunciator Expander Module LDM-E32 expands the
LDM-32 by 32 system points, to a maximum of 64 points total.
The LDM-R32 Relay Expander Module LDM-R32 provides the LDM-32 or
LDM-E32 with 32 dry Form-A (normally open) contacts.
16
The Annunciator Control
Module-32A/AFM-32A
contains 32 red alarm LEDs, a
system trouble LED, an ON
LINE/POWER LED, and a
local piezo sounder with a
silence/acknowledge switch.
The AFM-32A is fixed at
address "1," and will not
accept expanders.
The Annunciator Expander
Module-32A expands the
ACM-32A by 32 system points.
The AEM-32A is identical in frontal
appearance to the ACM-32A. One
expander module can be supported by an
ACM-32A, providing a maximum of 64 points.
The ACM-8R Annunciator Control Module
provides eight Form-C relays with 5 A contacts,
which can be used to track any group of eight zones
within the system.
AFP-200 Instruction
PN 15511:F2
10/11/99

Hide quick links:

Advertisement

Table of Contents
loading