To configure a CMX as a Form-C relay, the two tabs must be broken off of the module. Use a pair of needle-
nose pliers to break off each tab.
Connect the communications loop to CMX terminals 1 (–) and 2 (+). The CMX occupies one module address
on the loop. Set the rotary switches on the CMX to the particular loop address required.
Wire the common and the normally-open or normally-closed contacts to the CMX as required.
Note: Contacts are not rated for motor loads.
Resistive:
2 A @ 30 VDC
Inductive:
1 A @ 30 VDC (0.6 pf)
0.3 A @ 120 VDC (0.35 pf)
40
CMX-1
CMX-2
2 A @ 30 VDC
1 A @ 30 VDC (0.6 pf)
Pilot Duty: 0.6 A @ 30 VDC (0.35 pf)