In terminal mode, the control panel annunciates all point information to remote LCD-80 displays. Each
LCD-80 mirrors the front panel display and includes Acknowledge, Silence, and Reset switches. An LCD-80
will display all 198 intelligent points without being programmed. Switch SW2 on the circuit board must be set
for TERM and the control panel must be programmed for terminal mode.
In ACS mode, the control panel annunciates its 99 software zones. The use of software zones allows the user
to freely map any number of modules or detectors to a single LED. The ACS connection uses a standard
EIA-485 interface, capable of two-way, high speed communications with multiple annunciators located up to
6,000 ft. from the control panel.
When programmed for ACS mode, the control panel will support the following ACS-compatible modules:
Point annunciators
ACM-8R
ACM-16AT, AEM-16AT
ACM-32A, AEM-32A
AFM-16A, AFM-32A, AFM-16AT
LDM-32, LDM-E32, LDM-R32
LCD-80
The LCD-80 must be set to ACS mode (refer to the LCD-80 manual).
ACM-8R
This module may be used to increase the relay capacity of the control panel by providing mappable dry contact
relays. The control panel can support 99 detectors, 99 modules, four Notification Appliance Circuits, eight
internal relays, and 99 external relays, for a total of over 300 points. The ACM-8R may be powered by the
regulated/high-ripple notification appliance power from the control panel. For detailed information, refer to
ACM-8R manual.
Note: Similar point capacity extension is possible using the LDM-R32, but the LDM-32 series must use
filtered, regulated power and is therefore more limited than the ACM-8R.
ACS annunciation displays the 99 software zones of the control panel plus 8 system points, for a total of 107.
Information is transmitted using annunciator addresses 1 and 2. The EIA-485 interface will allow up to 32
annunciators (all but two must be in receive-only mode), over distances of up to 6,000 ft. (check power
limitations).
84
AFP-200 Instruction
PN 15511:F2
10/11/99