The AFP-200 control panel is completely field-programmable and requires no special software skills. Program-
ming may be done in one of two ways:
1. Using the Autoprogram feature and the control panel keypad. is a convenient way to quickly bring the
system on-line and to make changes to an existing system program. This chapter provides detailed instruc-
tions for programming the control panel using the keypad.
2. Using the Off-Line Programming Utility lets you create site-specific programming information using a
DOS-based computer and is the preferred method for programs requiring a large amount of data entry. This
chapter only provides instructions for uploading and downloading programs created off-line. For detailed
instructions, refer to the Off-Line Programming Utility manual.
Press the Enter key to enter programming mode and the display shows the Programming Entry screen:
To program the password, press 1. The LCD displays the following screen:.
There are two passwords, Program Change and Status Change. The Program Change password is factory set
There are two passwords, Program Change and Status Change. The Program Change password is factory set
at 00000, and Status Change is factory set at 11111. Passwords are user-definable and a method exists for the
at 00000, and Status Change is factory set at 11111. Passwords are user-definable and a method exists for the
identification of a forgotten password. If an invalid password is entered, the display shows, INVALID PASS-
identification of a forgotten password. If an invalid password is entered, the display shows, INVALID PASS-
WORD and an error code number. By contacting the manufacturer, the error code can be deciphered to identify
WORD and an error code number. By contacting the manufacturer, the error code can be deciphered to identify
the true password that exists in the machine. To exit from Program Change or Status Change operations at any
the true password that exists in the machine. To exit from Program Change or Status Change operations at any
time, press the Backspace key repeatedly, or press System Reset.
time, press the Backspace key repeatedly, or press System Reset.
If the correct programming password is entered, the control panel will enter Program Change mode. In Program
If the correct programming password is entered, the control panel will enter Program Change mode. In Program
Change mode, the trouble relay is activated, the piezo is off, and the System Trouble LED flashes (and cannot
Change mode, the trouble relay is activated, the piezo is off, and the System Trouble LED flashes (and cannot
be made steady). The LCD displays the following screen:
be made steady). The LCD displays the following screen:
At this point, a numeric key (0-8) must be pressed. Pressing the Backspace key will abort the operation.
At this point, a numeric key (0-8) must be pressed. Pressing the Backspace key will abort the operation.
AFP-200 Instruction
PN 15511:F2
1 = P R O G R A M M I N G
2 = R E A D @ S T A T U S @ E N T R Y
( B A C K S P A C E @ T O @ A B O R T )
E N T E R @ P R O G @ O R @ S T A T U S
P A S S W O R D , @ T H E N @ E N T E R .
( B A C K S P A C E @ T O @ A B O R T )
0 = C L R @ 1 = A U T O @ 2 = P O I N T
3 = P A S S W D @ 4 = M E S S A G E
5 = Z O N E S @ 6 = S P L @ Z O N E S
7 = S Y S @ 8 = C H E C K @ P R G
10/11/99
49