Connections are power-limited and supervised.
•
A maximum of 10 devices may be connected to this circuit (ACM, LDM, AFM, etc.).
•
6,000 feet is the maximum recommended distance (16 AWG) between the control panel and the furthest
annunciator.
•
Use twisted-pair cable with a characteristic impedance of approximately 120 ohms.
•
The EIA-485 circuit is rated 5.5 VDC max., 60 mA max.
•
Refer to the ACS Manual and the LDM Manual for additional information.
•
Set SW2 on the control panel to the "ACS" position.
90
TB2
TB2
T
B
6
TB5-1 (+)
TB5-2 ()
Install 120 ohm terminat-
ing resistor on last
annunciator
AFP-200 Instruction
PN 15511:F2
10/11/99