DNP 3.0
LAN/WAN Master
(OPC) 3.2
3.4.5.
26
COM600 Station Automation Series
User's Guide
Name
Value or Value range/ Default
Time Synchroniza-
Direct time synchronization
tion Function
Delay compensated
Time Synchroniza-
0 to 65535
tion Interval
Default: 0
Command Hand-
ling
Maximum Response
0 to 600
Time
Default: 15
Reply Timeout
0 to 65
Default: 10
Lengths
Information Address
1 to 3
Length
Default: 2
Control Authoriza-
tion
Station/Remote
User defined
Switch OPC Path
Configuring Logical Device properties
Table 3.4.5-1 Logical Device properties
Property/Parameter
Basic
Station/Remote Switch
OPC Path
Value or Value range/
Default
Description
Function code for Time Synchronization.
Time in seconds between device time
updates.
Maximum time in seconds that the master
station waits for a response to a command
request from the slave.
Maximum time in seconds that the DNP
3.0 application layer waits for a reply from
the slave.
Length of data object address used in DNP
3.0 messages.
OPC path of the station remote switch
position to be used with this device. The
format is Node#ProgID For OPC
Server#Channel Name\IED Name\Logical
Device Name\Logical Node Name\Data
Object Name E.g. GW#ABB.MOD-
BUS_SERIAL_OPC_DA_Server.Instance[1]#Chan-
nel[1\IED1\LD1\GGIO1\loc
Description
OPC path of the station remote switch
position to be used with this device. The
format is Node#ProgID For OPC
Server#Channel Name\IED
Name\Logical Device Name\Logical
Node Name\Data Object Name e.g.
GW#ABB.Mod-
bus_Serial_OPC_DA_Server.
Instance[1]#Channel1\IED1\LD1
\GGIO1\loc
1MRS756566