3.4.4.
24
COM600 series, Version 5.0
IEC 60870-5-103 Master (OPC) User's Manual

Configuring IEC103 Device properties

Table 3.4.4-1 lists the value ranges and/or default values for the IEC103 Device properties
that you can define. The actual configuration by using SAB600 is performed as described
in 3.4.1, General information about configuring objects.
Table 3.4.4-1 IEC103 Device properties
Name
Value or Value range/
Default
Basic
Diagnostics
True
Enabled
False
Default: False
In Use
In Use
Not In Use
Default: In Use
Simulation Mode
True
False
Default: False
Addresses
Polling Address
0...255
Default: 1
Station Address
0...255
Default: 1
Communication
Control
Complete Event
True
Time Tag From
False
Internal Clock
Default: True
Confirmation
0...255
Timeout
Default: 60
Prevents Auto-
True
matic Sending of
False
General Interroga-
tion
Default: True
Reply Timeout
0...255
Default: 10
Description
Specifies whether diagnostic AE events are sent
for the device.
Controls whether the device communication is
initially in use or not.
Specifies whether the device is in simulation mode
or not.
Station polling address
Common address of ASDU
Completion of event time tag by adding year, date,
and hour. If true, event time tags are completed
based on the internal clock of the master. If false,
time tags are completed based on clock informa-
tion sent by the slave.
Command confirmation timeout in seconds
Sending of general interrogation. If true, GI is not
sent. If false, GI is sent always when communica-
tion is (re)established successfully.
Link layer command acknowledgment timeout in
seconds