DNP 3.0
LAN/WAN Master
(OPC) 3.2
3.4.8.17.
3.4.8.18.
42
COM600 Station Automation Series
User's Guide
Controllable single point (SPC)
Table 3.4.8.17-1 Configurable SPC properties for OPC client
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
SPC
Class
Addresses
Control Index
-1 to 65535
Default: -1
Indication Index
-1 to 65535
Default: -1
Data Class Spe-
cific
Control Code Quali-
Momentary
fier
Pulse
Latch
Default: Momentary
Control Object
Default: Binary control output
block (12).
Control Variation
0 to 65535
Default: 1
Indication Object
Binary input (1, 2)
Binary output (10)
Default: Binary input (1, 2)
Operate
Direct Operate
Select Before Operate
Default: Direct Operate
Single point status (SPS)
Table 3.4.8.18-1 Configurable SPS properties for OPC client
Property/ Para-
Value or Value range/ Default
meter
Basic
Description
Common data class according to IEC
61850.
Control index.
Indication index.
Object number for control.
Variation for control.
Object number for indication.
Specifies using two-step, select-before-
operate method for issuing control request
or not.
Description
1MRS756566