Hinge (Pull) Side Mounting; Hinge (Pull) Side Installation - Assa Abloy Norton LEO 5700 Series Installation And Instruction Manual

Power operator with optional plug-in power input
Hide thumbs Also See for Norton LEO 5700 Series:
Table of Contents

Advertisement

14-3/16
15 (381)
Max. Distance
for Placement
of Power Input
Receptical
(shaded region)
1/2
(13)
1-1/8
(29)
3
(76)
C L Hinge
2" (51mm)
Min. Frame
Face
1-3/4" (44mm) Min.
Door Thickness
2-1/4" (57mm) Max.
Step 1: Determine hand of door from illustration on upper right of this
page.
Step 2: Using template above locate and prepare holes in the frame &
door:
Frame
A. Prepare six (6) holes for 1/4-20 machine screws or
No. 14 x 2-3/4" (70mm) wood screws. Blind rivet nuts (by others)
are suggested for unreinforced hollow metal frames or for
aluminum frames.
B. Concealed Class 2 Low Voltage Only: One (1) 7/8" (22mm)
diameter hole for conduit, for switch/sensor wires only.
NOTE: On new construction this hole will generally be drilled by
the frame supplier at their shop or at the time the frame is
installed in the wall.
Door
C. Prepare three (3) holes for 3/8" diameter sex nuts. Standard units
Page 4
1. Hinge (Pull) Side Mounting Instructions
A
(360)
13-13/16
(350)
12-15/16
(329)
7/8 (23) Dia.
1-7/16
(Class 2
(37)
Wiring Only)
11
(279)
Door Opening
Dim "A"
Angle
Up to 110°
15-1/2 (394)
111° to 180°
13-1/4 (337)
6" (152mm)
Min. Ceiling
Clearance
1A. Installation Sequence
Right Hand Door
opening to 110° shown.
13-7/16
(341)
7-9/16
(192)
Please verify desired mounting
requires Hinge (Pull) Side
application as shown on this
template.
22
(559)
Notes:
• All dimensions are given in inches (mm).
• Thickness recommended for reinforcements in hollow
metal doors and frames is charted on Page 2.
• Do not scale drawing.
• Right hand door shown.
• This template information based upon use of 5"
• Maximum frame reveal is 6-7/8" (175mm) for this
application.
• Conduit hole is Class 2 low voltage wiring ONLY.
!Due to the risk of the Power Cord becoming entrapped
in moving parts of the operator, door, or system, the
Power Cord must be kept clear of all moving parts.
Frame Reveal
are supplied with sex nuts and screws for 1-3/4" (44mm) thick door.
Sex nuts and screws for other door thicknesses are available to
order.
Step 3: Remove cover from the unit and set cover & cover screws aside.
Step 4: Mount unit to door frame. Select A or B below.
A. Concealed Class 2 Low Voltage Only:
side of backplate. Fasten unit to door frame (seven screws).
B. Surface Class 2 Low Voltage Only:
(seven screws). Mount conduit bracket (found in screw pack) to
unit's backplate with two screws provided. Connect wiring conduit
to bracket.
Step 5: Mount track assembly to door using 3 1/4-20 screws & sex nuts
with buffer assembly toward hinge. Open part of track to face
top of door.
(Continue to next page.)
13-13/16
(351)
1/4-20 Machine Screws
or No. 14 Wood Screws
(6 Places)
1-1/8"
(29)
3/8 Dia.
Sex Nuts
(3 Places)
(127mm) maximum width butt hinges. A separate
template is required for other conditions.
Note: Door must be visible by person
operating activation switch(es)
80-9357-0002-020 (01-12)
6"
(152mm)
Min.
Clearance
2" (51mm)
Min.
Frame Face
5/8
Stop
(15.9)
Frame
Rabbet
Frame
Stop/Soffit
Connect conduit to frame
Fasten unit to door frame