Assa Abloy Norton LEO 5700 Series Installation And Instruction Manual
Assa Abloy Norton LEO 5700 Series Installation And Instruction Manual

Assa Abloy Norton LEO 5700 Series Installation And Instruction Manual

Power operator with optional plug-in power input
Hide thumbs Also See for Norton LEO 5700 Series:

Advertisement

Quick Links

ASSA ABLOY
2
6
9
7
8
Item No. Description
1
Back plate
2
Door Closer (1601LAP or 1601BFLAP)
3
Motor Assembly (5700M)
4
Inverter (5700IN)
5
Cover (5700COV)
6
On/Off switch
7
Circuit Breaker
Tools required:
• 1/8" allen wrench (included)
• Flat blade screwdriver (potentiometer & terminal size)
• Screwdriver (Phillips size 2)
• Tape ruler
! If local code requires unit to be hard wired instead of using the
plug-in type power supply cord supplied with this version of the
unit, the unit MUST be returned to the manufacturer and
replaced with a unit designed to be hard wired.
! To reduce the risk of shock, this operator has a grounding type
plug, that has a third (grounding) pin. This plug will only fit into a
grounding type outlet. If the plug does not fit into the outlet,
contact a qualified electrician to install the proper outlet. Do not
change the plug in any way.
1
3
10
12
!
with Optional Plug-in Power Input
Installation and Instruction Manual
4
11
Item No. Description
8
120VAC Power Input (C14 Appliance)
9
Activation Inputs
10
Door Open/Closed Position Magnets
11
Optional RF Receiver
12
Power Supply - 1.1A 24V
13
18 inch max. Power Cord (not shown)
• Power drill and set of drill bits
• Center punch
• Wire stripper
• #7 drill 1/4-20 tap (metal frame install)
WARNINGS
! Always disconnect the main power to the operator prior to
servicing or cleaning.
! This operator is for indoor use only.
! To reduce the risk of injury or person, use the operator only with
Pedestrian Swing doors.
! 120VAC power supplied to the operator must be a dedicated
circuit from the main circuit breaker panel and must NOT be
connected into any building lighting system that operates
flourescent lights.
! Maximum door size: 48 in (1219mm) wide x 250 lb (113.4kg).
5700
Series
LEO
Power Operator
80-9357-0002-020 (01-12)
Patents 5,881,497; 7,316,096; 7,484,333
5
®

Advertisement

Table of Contents
loading

Summary of Contents for Assa Abloy Norton LEO 5700 Series

  • Page 1 ® 5700 Series Power Operator with Optional Plug-in Power Input Installation and Instruction Manual ASSA ABLOY 80-9357-0002-020 (01-12) Patents 5,881,497; 7,316,096; 7,484,333 Item No. Description Item No. Description Back plate 120VAC Power Input (C14 Appliance) Door Closer (1601LAP or 1601BFLAP)
  • Page 2: Table Of Contents

    Contents General Stop (Push) Side Installation Frame Reinforcement Table Electrical Installation Component Layout Input Power Configuration ADA / ANSI / UL Inverter Details Hinge (Pull) Side Mounting Accessory / Typical Installations Hinge (Pull) Side Installation Troubleshooting Stop (Push) Side Mounting General Information ! UL labeled fire or smoke barrier door assemblies require that General Templating Information:...
  • Page 3: Component Layout

    Component Layout INVERTER MOTOR ASSEMBLY BREAKER SWITCH 1600 SERIES CLOSER BODY BACKPLATE REED SWITCH OPEN / CLOSE POSITIONING CHAIN MAGNETS PINION EXTENSION / CLUTCH ASSEMBLY ACCESSORY ON/OFF SWITCH POWER SUPPLY CORD TERMINAL (125V / 10A RATED 18AWG (4-POSITION) 18 INCHES MAX., NEMA 5-15P POWER INPUT AND IEC320-C13 CONNECTORS.
  • Page 4: Hinge (Pull) Side Mounting

    1. Hinge (Pull) Side Mounting Instructions Right Hand Door 6” 14-3/16 opening to 110° shown. (152mm) (360) Min. 13-13/16 15 (381) (350) Clearance Max. Distance 12-15/16 13-13/16 for Placement (351) (329) of Power Input 13-7/16 Receptical (341) (shaded region) 1/4-20 Machine Screws 2”...
  • Page 5 1A. Installation Sequence Continued Closing Cycle – Make adjustments, as necessary, to the Step 6: Insert slide arm rod into slide arm tube setting the distance Sweep Speed "S" valve and Latch Speed "L" valve. See Fig. between the pinion square and the slide stud at 13-1/2” 2 below for location of valves.
  • Page 6: Stop (Push) Side Mounting

    2. Stop (Push) Side Mounting Instructions Left Right Hand Hand Left Hand Door Door Door 14-3/16 open to 110° shown. (360) 15 (381) Max. Distance 13-13/16 13-13/16 (351) (351) for Placement of Power Input 12-15/16 13-7/16 (329) Receptical (341) 1/4-20 Machine Screws (shaded region) or No.
  • Page 7: Electrical Installation

    2A. Installation Sequence Continued Step 10: Adjust Hydraulic valves using a 1/8” hex wrench to obtain Step 5: Install main arm onto pinion shaft of unit at a 90° angle to the proper door closing speeds. See following illustrations. Refer door frame.
  • Page 8: Input Power Configuration

    3. Electrical Connections and Final Setup Continued Step 5: Adjust Closing Position Magnet (See Fig. 3) - With door in the Step 7: Flip Breaker Switch to “RESET” to turn power on. Jump closed position, use finger to slide Closed Position Magnet terminals 1 and 2 (as shown in Fig.
  • Page 9: Inverter Details

    Inverter Details DESCRIPTION FUNCTION CW - Increase M/DLY Motor Delay on Opening CCW - Decrease 115Y CW - Increase OBSTR SENS Obstruction Detection on Open CCW - Decrease CW - Increase TB501 REV SPD Motor Reversing Speed CCW - Decrease CW - Increase H/O TM Hold Open Time (5 - 30 Seconds)
  • Page 10 Radio Frequency Function Option Notes: 1. Power input to Door Operator Unit is at Optional 1.1A 24V “T1” Power Input Terminal (not shown) Power Supply 120VAC 60Hz. (AC) 2. Radio Frequency Feature can be purchased as a separate kit. Optional Door 2 Door 1 ORANGE RECEIVER...
  • Page 11: Troubleshooting

    Something jammed beneath the door Remove object ASSA ABLOY 3000 Highway 74 East • Monroe, NC 28112 Norton ® is a registered trademark of Yale Security Inc., an ASSA ABLOY Group company. An ASSA ABLOY Group Co. Tel: (877)- 974-2255 •...
  • Page 12 This page intentionally left blank.