AE8-1376 R5
DANGER

6. Controller Wiring

Always disconnect and lockout the power supply before beginning electrical
WARNING
installations or troubleshooting.
CAUTION
6.1 Non-Fan Cycling Wiring Schematic
NOTICE
CAUTION
16FLA/96LRA
Max
16A
1
3 4 5
Comp
Comp
Line
Line
HP saf. Press. D.i.
HP saf. Press. D.i.
Figure 6 – Non-Fan Cycling Wiring Schematic
Compressor: Use terminals 1-3.
Power Supply: Use terminals 4-5 (terminals 4 and 5 are
for power supply at 110VAC or 230VAC, depending on
the model).
Suction Pressure Transducer: Use terminal 9 (+5V)
for supply, terminal 11 for ground, and terminal 12 for
signal.
Condenser Temperature Sensor: Connect probe to
terminal 11 (ground) and 10.
Thermostat Digital Input: Use terminals 14-17.
UL HP input: Use terminals 15-17.
DLT Sensor: Connect probe to terminals 16-17.
Copeland PerformanceAlert (CPA): See Figure 8.
© 2015 Emerson Climate Technologies, Inc.
Application Engineering
B
U
9
10 11 12
13
14 15 16 17
Gnd
Gnd
+5V
Configurable input
Configurable input
Thermost. D.i.
Thermost. D.i.
Performance alert input or
Performance alert input or
Discharge line thermistor (DLT)
Discharge line thermistor (DLT)
L
L
E

6.2 Fan Cycling Wiring Schematic

16FLA/96LRA
Max
8(3)A250V~
16A
1
2
3
4 5 6 7 8
FAN2
Comp
FAN2
Comp
Line
Line
Figure 7 – Fan Cycling Wiring Schematic
Compressor: Use terminals 1-3.
Power Supply: Use terminals 4-5 (terminals 4 and 5 are
for power supply at 110VAC or 230VAC, depending on
the model).
FAN 1: Use terminals 6-7.
FAN 2: Use terminals 1-2.
Suction Pressure Transducer: Use terminal 9 (+5V)
for supply, terminal 11 for ground, and terminal 12 for
signal.
Condenser Temperature Sensor: Connect probe to
terminal 11 (ground) and 10.
Thermostat Digital Input: Use terminals 14-17.
UL HP input: Use terminals 15-17.
DLT Sensor: Connect probe to terminals 16-17.
Copeland PerformanceAlert (CPA): See Figure 8.
7-12
T
I
N
May 2016
9
10 11 12
13
14 15 16 17
N.C.
Gnd
Gnd
+5V
FAN1
FAN1
Configurable input
Configurable input
Thermost. D.i.
Thermost. D.i.
Performance alert input or
Performance alert input or
Discharge line thermistor (DLT)
Discharge line thermistor (DLT)
HP saf. Press. D.i.
HP saf. Press. D.i.