PRESSURE LOSS OF HYDRAULIC SYSTEM
The two curves represented in the diagram below indicate the
pressure drop on the battery to the water of pre-treatment and
post-treatment of the air in the dehumidi er. The dehumidi er
is tted with separate external attacks for pre-treatment and
post-treatment coils. It is possible, therefore, to feed the batteries
separately with two independent lines of adduction or connected
in parallel near the dehumidifier. The particular geometric
con guration automatically shares the ow on the two batteries
at a rate of 2/3 on that of the pre-treatment and 1 / 3 on that of
post-treatment whenever the feed is in parallel on the two coils.
45
40
35
30
25
20
15
10
5
0
0
0,5
1
Pre-treatment
Pre trattamento
Post-treatment
Post trattamento
Pressure Loss of Pre- and Post-treatment Exchanger
Perdite di carico scambiatori di Pre e Post trattamento
1,5
2
2,5
3

PERDITA DI CARICO DEL CIRCUITO IDRAULICO

Le due curve rappresentate nel diagramma sottostante indicano
le perdite di carico sulle batterie ad acqua di pretrattamento e
postrattamento dell'aria nel deumidificatore. Il deumidificatore
è predisposto con attacchi esterni separati per le batterie di
pretrattamento e postrattamento.
È possibile quindi alimentare le batterie separatamente con
due linee di adduzione indipendenti o collegarle in parallelo
in prossimità del deumidificatore.
La particolare configurazione geometrica ripartisce
automaticamente la portata sulle due batterie in ragione di
2/3 su quella di pretrattamento ed 1/3 sul postrattamento
qualora l'alimentazione sia in parallelo sulle due batterie.
3,5
4
4,5
5
Flow [liters/minute]
Portata [litri/minuto]