OEM Softener System Setup
Step 1S -
Press NEXT and simultaneously for 5 seconds and release. If screen in Step 2S does not
Step 1S
appear, the lock on valve programming has been activated. To unlock press , NEXT, , REGEN in
sequence, then press NEXT and simultaneously for 5 seconds and release.
Step 2S –
Choose SOFTENING using or . Press NEXT to go to Step 3S. Press REGEN to exit OEM
Step 2S
Softener System Setup.
Step 3S –
Choose Brining Direction using or . This screen is not viewed when Step 2S is set to
Step 3S
Filtering. Press NEXT to go to Step 4S. Press REGEN to return to previous step.
Step 4S –
Set Refill location using or :
Step 4S
• "PoST" to refill the brine tank after the final rinse; or
• "PrE" to refill the brine tank four hours before the regeneration time set.
This screen is not viewed when Step 2S is set to Filtering.
Press NEXT to go to Step 5S. Press REGEN to return to previous step.
Step 5S –
Select the time for the first cycle using or . For valve types 1.5 and 2.0, "oFF" is also
Step 5S
available.
Press NEXT to go to Step 6S. Press REGEN to return to previous step.
Step 6S –
Select the time for the second cycle using or . For valve types 1.5 and 2.0, "oFF" is also
Step 6S
available.
NOTE: The display will flash between cycle number and time, and brine direction (UP or dn).
Press NEXT to go to Step 7S. Press REGEN to return to previous step.
Step 7S –
Select the time for the third cycle using or . For valve types 1.5 and 2.0, "oFF" is also
Step 7S
available.
Press NEXT to go to Step 8S. Press REGEN to return to previous step.
Step 8S –
Select the time for the fourth cycle using or . For valve types 1.5 and 2.0, "oFF" is also
Step 8S
available.
Press NEXT to go to Step 9S. Press REGEN to return to previous step.
14