Potentiometer
The potentiometer
The output voltage is set to the rated value at the factory and can be set within certain limits;
for example, to compensate voltage drops across long supply lines to the connected load.
Figure 2-3
Type
6EP7133-6AB00-0BN0
6EP7133-6AE00-0BN0
NOTICE
Thermal overload possible
When adjusting the output voltage to greater than the rated voltage, the output current must
be derated by 4 %/V, or the permissible ambient temperature must be taken into account
with 3° C/V.
Note
It is only permissible to use an insulated screwdriver when actuating the potentiometer.
For information on actuating the potentiometer (screwdriver, torque), see Figure 2-2
Terminal data (Page 10).
SIMATIC ET200SP PS
Manual, 03.2018, A5E43207434
⑤
on the front of the device is used to set the output voltage.
Potentiometer
Factory setting
24 V
Description, device design, dimension drawing
Adjustment range
22.8 - 28 V
2.3 Potentiometer