Description, device design, dimension drawing

1.2 Connections and terminal designation

1.2
Connections and terminal designation
The line input terminals
output terminals
Installation (Page 17)).
Connections and terminal designations
Figure 1-2
1.3

Potentiometer

The potentiometer
voltage is set to the rated value at the factory and can be set within certain limits; for
example, to compensate voltage drops across long supply lines to the connected load.
Actuation of the potentiometer is allowed only be means of an insulated screwdriver.
Notes on potentiometer operation (such as a screwdriver, torque) refer to Chapter
Connections and terminal designation (Page 10), Fig. Terminal data.
10
to be supplied are used to connect the loads (see also Section
Supply input L1, N
Output +
Output –
Terminal data
on the front of the device is used to set the output voltage. The output
WARNING
can be used to establish the connection to supply voltage. The
One screw terminal each for 0.5 to 2.5 mm²
2 screw terminals for 0.5 mm to 2.5 mm²
2 screw terminals for 0.5 mm to 2.5 mm²
Type
5 V
12 V
15 V
24 V
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
Factory setting
Setting range
5 V
4.6 to 5.4 V
12 V
10.5 to 12.9 V
15 V
13.9 to 16.1 V
24 V
22.2 to 26.4 V
LOGO!Power