Potentiometer - Siemens SITOP PSU6200 3ph Equipment Manual

Table of Contents

Advertisement

2.3

Potentiometer

The potentiometer
voltage is set to the rated value at the factory and can be set within certain limits; for
example, to compensate voltage drops across long supply lines to the connected load.
Figure 2-4
Type
6EP3433-7SB00-0AX0
6EP3434-7SB00-3AX0
6EP3436-7SB00-3AX0
NOTICE
Thermal overload possible
When adjusting the output voltage to greater than the rated voltage, the output current must
be derated by 4 %/V, or the permissible ambient temperature must be taken into account
with 3 °C/V.
Note
It is only permissible to use an insulated screwdriver when actuating the potentiometer.
For information on actuating the potentiometer (screwdriver, torque), see Connections and
terminal designation (Page 10).
SITOP PSU6200 3ph
Equipment Manual, 02.2020, A5E44623402-1-76
on the front of the device is used to set the output voltage. The output
Potentiometer
Factory setting
24 V
Description, device design, dimension drawing
Adjustment range
24 V - 28 V
2.3 Potentiometer
11