Each change (rising or falling edge) detected in the status of a digital input is time-
tagged at an accuracy of ±1 ms. The time tag represents the moment (time) of the
latest input change of the value attribute. The time is not recorded until the filtering
time of the status change has elapsed, which means that the filtering time does not
affect the time tag value.
Count (BI#Count)
The count attribute indicates the number of positive input transitions of a filtered
input. The frequency range of a digital input parameterized to operate as a pulse
counter is 0...100 Hz. If a digital input is changed into a pulse counter, the attribute
BI# is frozen at the value valid at the moment of the change.
The example below shows how the attributes of the digital input 1 (PSC_7_BI1 on
PSC1 module) of REC 523 are named for the configuration:
PSC_7_BI1IV; digital input invalidity
PSC_7_BI1; digital input value
PSC_7_BI1Time; time tag
PSC_7_BT1Count; counter value

Digital outputs

General

The outputs of REC 523 are categorized as follows:
• HSPO High-speed power output, double-pole contact.
• SO Signal output, either NO (Normally Open) or NO/NC (Normally Open/
Normally Closed) contact.
Table 5.5.1-1
REC 523 digital outputs
REC 523
Outputs
PSC_7_HSPO1
PSC_7_HSPO2
PSC_7_SO1 (Heater output)
BIO1_3_SO1
BIO1_3_SO2
BIO1_3_SO3
BIO1_3_SO4
BIO1_3_SO5
BIO1_3_SO6
Outputs / total
9
The events and parameters of I/O cards can be found in the event and parameter lists
on the CD-ROM Technical Descriptions of Functions (refer to Section 1.8. Related
documents).
For detailed information about terminal connections for the outputs, please refer to
the terminal diagrams, where all the outputs and relay connector terminals are
presented.