ABB REC 523 Technical Reference Manual page 63

Remote monitoring and control unit
Table of Contents

Advertisement

1MRS750881-MUM
Remote Monitoring and Control Unit
Technical Reference Manual
Table 7.1.-9
Environmental conditions (Continued)
Damp heat test, cyclic
Storage temperature tests
Table 7.1.-10 Standard tests
Insulation tests
Dielectric test
IEC 60255-5
Impulse voltage test
IEC 60255-5
Insulation resistance
measurements
IEC 60255-5
Mechanical tests
Vibration tests (sinusoidal)
Shock and bump test
Table 7.1.-11 Electromagnetical compatibility tests
The EMC immunity test level fulfills the requirements specified below
1 MHz burst disturbance
common mode
test, class III,
differential mode
IEC 60255-22-1
Electrostatic discharge
for contact discharge
test, class III,
for air discharge
IEC 61000-4-2 and
IEC60255-22-2
Radio frequency
conducted, common
interference test
mode
IEC 61000-4-6 and
IEC 60255-22-6
radiated, amplitude-
modulated
IEC 61000-4-3 and
IEC 60255-22-3
radiated, pulse-
modulated
ENV 50204
Fast transient
power supply
disturbance test
I/O ports
IEC 60255-22-4 and
IEC 61000-4-4
Surge immunity test
power supply
IEC 61000-4-5 and
IEC 60255-22-5
I/O ports
Power frequency (50 Hz)
100 A/m
magnetic field
IEC 61000-4-8
Voltage dips and
30%, 10 ms
short interruptions
60%, 100ms
IEC 61000-4-11
60%, 1000ms
>95%, 5000ms
according to IEC 60068-2-30
r.h. = 95%, T = 25°...55°C
according to IEC 60068-2-48
Test voltage
2 kV, 50 Hz, 1 min.
Test voltage
5 kV, unipolar impulses,
waveform 1,2/50 µs, source
energy 0.5 J
Insulation
> 100 MΩ, 500 V DC
resistance
IEC 60255-21-1, class I
IEC 60255-21-2, class I
2.5 kV
1.0 kV
6 kV
8 kV
10 V (rms),
f = 150 kHz...80 MHz
10 V/m (rms),
f = 80...1000 MHz
10 V/m, f = 900 MHz
4 kV
2 kV
4 kV, line to earth
2 kV, line to line
2 kV, line to earth
1 kV, line to line
REC 523
63

Advertisement

Table of Contents
loading

Table of Contents