REC 523
5.5.2.
5.5.2.1.
5.5.2.2.
40
Remote Monitoring and Control Unit
Technical Reference Manual
For detailed technical data of the outputs, refer to Section 7.1. Technical data.
Configuration
High speed double-pole power output (HSPO)
The high-speed power outputs PSC_7_HSPO1 and PSC_7_HSPO2 can be
connected as double-pole outputs where the object to be controlled (for example a
circuit breaker) is electrically connected between the two relay contacts, see figure
below. The high-speed double-pole power output is preferred for the control of
disconnectors.
e.g.
PSC_7_HSPO1
PSC_7_HSPO2
Fig. 5.5.2.1.-1 High-speed double-pole power outputs PSC_7_HSPO1 and
PSC_7_HSPO2
The high-speed power outputs PSC_7_HSPO1 and PSC_7_HSPO2 can also be
connected as single-pole power outputs where the object to be controlled (for
example a circuit breaker) is electrically connected in series with the two relay
contacts, see Fig. 5.5.2.1.-2 .
e.g.
PSC_7_HSPO1
PSC_7_HSPO2
Fig. 5.5.2.1.-2 High-speed single-pole power output (HSPO)
Signalling output (SO)
The signalling output is not a heavy-duty output and thus it cannot be used for
controlling a disconnector without external interpose relays. Available SO contacts
are either Normally Open or Normally Open/Normally Closed type contacts (NO or
NO/NC), see the figure below.
+
CB coil
-
+
CB
-
1MRS750881-MUM
cbcoil2
doubpol2