Page 1
8902/LS Line Synchronization Option aerospace aerospace 北京润诚时代科技有限公司 北京润诚时代科技有限公司 北京润诚时代科技有限公司 climate control climate control electromechanical 自动化事业部 自动化事业部 fi ltration fi ltration 地址:北京市朝阳区汤立路218号C座968室 地址:北京市朝阳区汤立路218号C座968室 fl uid & gas handling fl uid & gas handling 邮编:100012 邮编:100012 hydraulics hydraulics 电话:010-84450370 电话:010-84450370 pneumatics pneumatics 传真:010-84450371...
Page 3
Parker SSD Drives company without written permission from Parker SSD Drives, a division of Parker Hannifin Ltd. Although every effort has been taken to ensure the accuracy of this document it may be necessary, without notice, to make amendments or correct omissions.
Page 4
Parker or its subsidiaries or authorized distributors. To the extent that Parker or its subsidiaries or authorized...
Page 5
Safety Information Requirements IMPORTANT: Please read this information BEFORE installing the equipment. Intended Users This manual is to be made available to all persons who are required to install, configure or service equipment described herein, or any other associated operation. The information given is intended to highlight safety issues, EMC considerations, and to enable the user to obtain maximum benefit from the equipment.
Page 6
Safety Information Hazards DANGER! - Ignoring the following may result in injury 1. This equipment can endanger life by exposure to 5. For measurements use only a meter to IEC 61010 rotating machinery and high voltages. (CAT III or higher). Always begin using the highest range.
Contents Contents Page YNCHRONIZATION PTION Description....................... 1 • Features ....................1 • Part Number ................... 1 • Used On ....................1 Recommended Spare Parts ..................1 Installation....................... 2 Fitting the LA471892U001 Attenuator module............. 2 DIP Switch Settings on 8902-LS-00................2 Fitting the 8902-LS-00 ....................
890CD Common Bus Drive 890PX/.. 890PX high power drive Refer to the 890 Engineering Reference Manual, Appendix E for Product Code details. Recommended Spare Parts We recommend that you keep one option as a spare to reduce downtime. 8902/LS Line Synchronization Option...
DIP Switch Settings on 8902-LS-00 The switch settings control the following inputs: Input Threshold Switch Number Input Controlled not used 3V±1 8V±1 Set all switches to the ON position (3V). Figure 1 Option board showing DIP Switch location 8902/LS Line Synchronization Option...
9. Replace the control board (with attached options) into the drive. Tighten screws (A). 10. Tighten the Option A and Option B screws; or importantly, fit the Figure 3 Rear blank covers and secure with the screws. of Control 8902/LS Line Synchronization Option...
8902-LS-00 card fitted in the drive. See figure 4 on the next page. Use twisted-pair, screened cable, preferably with an overall screen and a screen over each individual pair. Recommended cable: Three pairs individually screened, plus overall screen, characteristic impedance 100 to Ω , e.g. Belden 8163 8902/LS Line Synchronization Option...
Page 13
3-phase supply 400-690VAC, 40-70 Hz Attenuator module L 3 L 2 L 1 X37 connector Shield Supply Figure 4: Wiring Diagram 8902/LS Line Synchronization Option...
Initial Set-up Configuring the 890 AFE Use the DSE (Lite) Configuration Tool to configure the drive. The DSE Lite Configuration Tool is Parker SSD Drives’ Windows-based block Note: programming software and is supplied with each drive. File/New/890/v3 v3_AFE.890 Under , select the template.
Cabling Requirements Supply Cable Signal/Control Cable Cable Type Unscreened Screened (for EMC Compliance) Segregation From all other wiring From all other wiring (clean) (sensitive) Length Limitations 25 metres Screen to Earth Connection Drive end only 8902/LS Line Synchronization Option...
Do not dispose of in a land fill site set aside for domestic waste. Packaging During transport our products are protected by suitable packaging. This is entirely environmentally compatible and should be taken for central disposal as secondary raw material. 8902/LS Line Synchronization Option...
When installed in accordance with this manual, the Line Synchronization Attenuator is CE marked by Parker SSD Drives in accordance with the low voltage directive (S.I. No. 3260 implements this LVD directive into UK law). An EC Declaration of Conformity (low voltage directive) is included at the end of this chapter.
1. Emission - these standards limit the interference caused by operating (this) drive module. 2. Immunity - these standards limit the effect of interference (on this unit) from other electrical and electronic apparatus. Conformance can be demonstrated using the Product Specific Standard. 8902/LS Line Synchronization Option...
Dr Martin Payn ( Conformance Officer) * Compliant with the immunity requirements of the Standard without specified EMC filters. PARKER HANNIFIN LTD, AUTOMATION GROUP, SSD DRIVES EUROPE NEW COURTWICK LANE, LITTLEHAMPTON, WEST SUSSEX BN17 7RZ TELEPHONE: +44(0)1903 737000 FAX: +44(0)1903 737100 Registered Number: 4806503 England.