Dual Position Solenoid Valve
Type S4AD
Port Size: 20 mm to 100 mm (3/4" – 4")
For Ammonia, R-22 and
other common Refrigerants
Features
• Prevents the damaging effects of vapor
propelled liquid
• Combined use as a hot gas and soft gas
valve
• Integrated S6A Pilot Solenoids
• Standard Coil Housing Meets NEMA 3R
and NEMA 4 - Rain Tight
• Reduces installed costs
• Pilot Light Available
• Manual Opening Stem
• Maximum Rated Pressure (MRP): 27.6 bar
(400 psig)
Fig 1
Refrigerating Specialties Division
311446
Bulletin 30-95C
May 2007
Service and Installation
Description
The S4AD is based on the same valve body, principles,
and length dimension as the standard S4A valves
making for easy field replacements. This heavy duty
solenoid valve is suitable for ammonia, R-22, other
refrigerants, and certain oils and other fluids approved
for use in refrigeration. The S4AD is a pilot operated,
dual-position, normally closed valve. aIt will close on
power failure. The S4AD may be opened by means of
the manual opening stem for servicing or in case of
electrical power failure.
The Type S4AD Solenoid Valve is furnished with FPT
Internal NPT (U.S. Standard Taper Pipe Thread), Socket
Weld, Weld Neck or ODS (solders over copper tubing of
given diameter) connections. The valve may be easily
removed from between the flanges for servicing.
It is advisable to install as strainer upstream of each
valve to prevent entrance of foreign material into
the valve and the rest of the system. Refrigerating
Specialties strainers are available to close-couple to
valve inlets.
Purpose
The S4AD is a spring closing valve, suitable for use in
refrigerant liquid, hot gas or suction lines in a tem-
perature range of -45° to 105° C (-50° to 220° F).
1
I S O
9 0 0 1 - 2 0 0 0 C E R T I F I E D

Advertisement

Table of Contents
loading

Summary of Contents for Parker S4AD

  • Page 1 • Manual Opening Stem • Maximum Rated Pressure (MRP): 27.6 bar (400 psig) May 2007 Service and Installation Description The S4AD is based on the same valve body, principles, and length dimension as the standard S4A valves making for easy field replacements. This heavy duty solenoid valve is suitable for ammonia, R-22, other refrigerants, and certain oils and other fluids approved for use in refrigeration. The S4AD is a pilot operated, dual-position, normally closed valve. aIt will close on power failure. The S4AD may be opened by means of the manual opening stem for servicing or in case of electrical power failure. The Type S4AD Solenoid Valve is furnished with FPT Internal NPT (U.S. Standard Taper Pipe Thread), Socket Weld, Weld Neck or ODS (solders over copper tubing of given diameter) connections. The valve may be easily removed from between the flanges for servicing. It is advisable to install as strainer upstream of each valve to prevent entrance of foreign material into the valve and the rest of the system. Refrigerating...
  • Page 2: Principles Of Operation

    (108723) which can be used to control the solenoid valve is typically appliedas a combination hot gas valve sequencing. and soft gas valve or as a liquid solenoid. Manual Opening Stem Principles of Operation The manual opening stem on the Type S4AD is for the The Type S4AD is a pilot operated dual-position so- purpose of opening the valve without energizing the lenoid. The valve includes two solenoid assemblies. solenoid coil. For access to the stem the seal cap on When both solenoids coils are energized the main valve the bottom of the valve must be removed. This must be is 100% open. With solenoid coil #2 is energized, the done with caution as refrigerant may have been trapped valve is open approximately 10% of its' full stroke.
  • Page 3 Unless troubled with actual coil burnouts, high coil temperature should Service Pointers be ignored. Persistent burnouts indicate improper line or coil voltage. See (1e) above. The S4AD Solenoid Valve and Strainer are easily re- movable for cleaning or repairing. To remove valve and strainer, first manually open the valve and pump out the refrigerant in the section of the line sealed off. Then unscrew the flange bolts and spread the flanges slightly apart. 1. Failure to Open: (a) Coils are of incorrectly high voltage. See “Electrical.“ Check voltage printed on the coil. (b) Line voltage is abnormally low. See...
  • Page 4 S4AD Fig 2 Refrigerating Specialties Division...
  • Page 5 20mm 25mm 32mm 40mm 50mm 65mm 75mm 100mm 20mm 25mm 32mm 40mm 50mm 65mm 75mm 100mm Item No. Description Qty. 3/4” 1” 1-1/4” 1-5/8” 2” 2-1/2” 3” 4” Item No. Description Qty. 3/4” 1” 1-1/4” 1-5/8” 2” 2-1/2” 3” 4” Plunger/Needle Asm.
  • Page 6 S4AD Fig 3 PORT SIZE mm in. mm in. mm in. mm in. mm in. Conn. mm Conn. 3/4" 25.4 10.0 1-1/8" 28.7 11.3 20-25 3/4"&1" 39.9 15.7 14.7 5.8 15.7 6.2 24.6 9.7 17.0 6.7 1" 26.2 10.3 21.6 8.5 1-3/8"...
  • Page 7 R/S Defrost Controller Wiring Diagram CK-2D/CK-6D Line Equilization, S4AD Soft Start Note:The above wiring diagram is to be used only for a R/S defrost controller. If other manufacturer's controller is used, please consult their electrical diagram R/S Adjustable Time Delay Wiring Diagram...
  • Page 8: Warranty

    All hand valves isolating such sections should be marked, warn- ing against accidental closing, and must not be closed until the liquid is removed. Check valves must never be installed upstream of solenoid valves, or regulators with electric shut-off, nor should hand valves upstream of solenoid valves or downstream of check valves be closed until the liquid has been removed. It is advisable Parker Hannifin Corporation • Refrigerating Specialties Division 2445 South 25th Avenue • Broadview, IL 60155-3891 Telephone (708) 681-6300 • Fax (708) 681-6306...

Table of Contents