Sine-wave filter
Hide thumbs Also See for SINAMICS G130:

Advertisement

Electrical installation
Connection
When connecting the sine-wave filter, you must take into account the following conditions to
ensure that the filter functions correctly:
● With analog control cables, connecting the shield at both ends can result in coupled-in
● Control cables must be routed separately from power cables. Power cables are motor
● The cross-sections of the connection cables to 1U1, 1V1, 1W1 and to 1U2, 1V2, 1W2
● You must use shielded motor cables. The shield for the motor cable must be attached to
● The ground wire for the motor must be fed directly back to the Power Module.
18
noise. To prevent this, the shield must only be connected at one end on the Power
Module.
cables or connecting cables from the DC link of the Power Module (terminals
DCPA/DCNA) to other components (e.g., Braking Module). In particular, you must ensure
that control cables and power cables are not routed in parallel in a joint cable raceway,
even if all the cables are shielded.
must be identical, and must be dimensioned appropriately for the current-carrying
capacity and routing method (see Chapter "Technical Specifications" in the SINAMICS
G130 operating instructions).
the shield plate and motor housing.
Operating Instructions, 05/2010, A5E00992420A
Sine-wave filter