Sine-wave filter
Hide thumbs Also See for SINAMICS G130:

Advertisement

Table 2- 2
6SL3310-1GE32-1AAx
6SL3310-1GE32-6AAx
6SL3310-1GE33-1AAx
6SL3310-1GE33-8AAx
6SL3310-1GE35-0AAx
The values apply to operation with a sine-wave filter and do not correspond with the rated
1)
current on the type plate.
Commissioning
When commissioning using the STARTER or AOP30, the sine-wave filter must be activated
by means of appropriate selection screenforms or dialog boxes (p0230 = 3), see the section
"Commissioning" in the SINAMICS G130 Operating Instructions.
The following parameters are changed automatically during commissioning.
Table 2- 3
Parameter settings for sine-wave filters with SINAMICS G130
Parameters
p0230
Drive filter type, motor side
p0233
Power unit motor reactor
p0234
Power unit sine-wave filter capacitance
p0290
Power unit overload response
p1082
Maximum speed
p1800
Pulse frequency
p1802
Modulator mode
p1909
Motor data identification, control word
Note
When the factory settings are restored, parameter p0230 is reset.
The parameter must be reset if the system is commissioned again.
Sine-wave filter
Siemens Industrial
Operating Instructions, 05/2010, A5E00992420A
Technical specifications for sine-wave filters with SINAMICS G130
Order number
SINAMICS G130
6SL3310-1GF31-8AAx
6SL3310-1GF32-2AAx
Name
Voltage
Pulse frequency
[V]
3 AC 380 – 480
3 AC 380 – 480
3 AC 380 – 480
3 AC 380 – 480
3 AC 380 – 480
3 AC 500 – 600
3 AC 500 – 600
3: Siemens sine-wave filter
Filter inductance
Filter capacitance
Disable pulse frequency reduction
Fmax filter / pole pair number
Nominal pulse frequency of the filter (see previous table)
Space-vector modulation without overmodulation
Rs measurement only
Output current
[kHz]
[A]
4
172 A
4
216 A
4
273 A
4
331 A
4
382 A
2.5
152 A
2.5
187 A
Setting
General
1)
13