Summary of Contents for Pepperl+Fuchs VisuNet EX2 GMP
RM/PC 3700 Series
Page 1
PROCESS AUTOMATION MANUAL VisuNet EX2 GMP RM/PC 3700 Series Hardware Manual...
Page 2
VisuNet EX2 GMP RM/PC 3700 Series With regard to the supply of products, the current issue of the following document is ap- plicable: The General Terms of Delivery for Products and Services of the Electrical Indus- try, published by the Central Association of the Electrical Industry (Zentralverband Elektrotechnik und Elektroindustrie (ZVEI) e.V.) in its most recent version as well as the supplementary clause: "Expanded reservation of proprietorship"...
VisuNet EX2 GMP RM/PC 3700 Series Safety Safety Validity The chapter “Safety” is valid as instruction manual. Specific processes and instructions in this instruction manual require special provisions to guarantee the safety of the operating personnel. Symbols Used This document contains symbols for the identification of warning messages and of informative messages.
VisuNet EX2 GMP RM/PC 3700 Series Safety Reference to Further Documentation Observe laws, standards, and directives applicable to the intended use and the operating location. Observe Directive 1999/92/EC in relation to hazardous areas. The corresponding datasheets, manuals, declarations of conformity, EU-type examination certificates, certificates, and control drawings if applicable (see datasheet) are an integral part of this document.
VisuNet EX2 GMP RM/PC 3700 Series Safety 1.6.1 Intended Use The device is only approved for appropriate and intended use. Ignoring these instructions will void any warranty and absolve the manufacturer from any liability. The device must only be operated in the specified ambient temperature range and at the specified relative humidity without condensation.
Page 9
VisuNet EX2 GMP RM/PC 3700 Series Safety Rated voltage 20 ... 30 VDC (SELV) Connection X1: 1 ... 4 Rated current < 2.5 A Maximum safe voltage U 60 V Interface type 1 Ethernet (Ex ec) Connection X2: 1 ... 8 Rated voltage 30 V Rated current...
Page 10
VisuNet EX2 GMP RM/PC 3700 Series Safety Voltage U Current 150 mA Power P 1.4 W Characteristic curve rectangular For gas group IIC: C o = 2.4 μF L o = 3 mH Lumped capacitances OR inductances For gas group IIB: C o = 42 μF L o = 10 mH Technical Data VisuNet EX2 GMP PC/RM 3721-* Version VisuNet EX2 GMP Interface type existent...
Page 11
VisuNet EX2 GMP RM/PC 3700 Series Safety Connection X2: 1 ... 8 Rated voltage 30 V Rated current 400 mA Maximum safe voltage U 60 V Interface type 2 Serial interface RS 485/RS 232 (Ex ec) Connection X3: 1 ... 4 Rated voltage ±15 V Rated current...
Page 12
VisuNet EX2 GMP RM/PC 3700 Series Safety Technical data VisuNet EX2 GMP PC/RM 3722-* Version VisuNet EX2 GMP Interface type existent PC/RM3722-*-A1-****-*********-S0 X1 - X5 PC/RM3722-*-A1-****-*********-S3 X1 - X6 PC/RM3722-*-A1-****-*********-A3 VisuNet EX2 GMP PC/RM 3722-* Supply Input voltage range 20 ... 30 V DC (SELV) Power consumption max.
VisuNet EX2 GMP RM/PC 3700 Series Safety Rated current 200 mA Maximum safe voltage U 60 V Interface type 3 USB (Ex ec) Connection X3: 5 ... 8 Rated voltage Rated current < 500 mA Maximum safe voltage U 60 V Interface type 4 USB (Ex ic) Connection...
Labelling VisuNet EX2 GMP PC/RM37** VisuNet EX2 GMP PC/RM 3719-*-A1-* VisuNet EX2 GMP PC/RM3719-*-A1* Pepperl+Fuchs GmbH 68307 Mannheim, Germany PF 16 CERT B0F0 X II 3G Ex ic ec [ic] IIC T4 Gc II 3D Ex ic tc [ic] IIC T85°C Dc Ambient temperature: 0 °C ...
VisuNet EX2 GMP RM/PC 3700 Series Safety 1.10 Labelling keyboard EXTA3-* Keyboard EXTA3-* EXTA3-* Pepperl+Fuchs GmbH 68307 Mannheim, Germany PF 11 CERT 1918 X II 3G Ex ic IIC T4 Gc II 3D Ex ic IIIB T135°C Dc File E190294...
There are no means provided to perform routine field maintenance on this device. Caution! Do not repair, modify, or manipulate the device. If there is a defect, always send back the device to Pepperl+Fuchs. Hazardous Area 1.13.2 Dust Zone 22, Class II/Div 2 The housing must not be opened when the device is connected to the supply voltage if there is a risk of dust explosion.
VisuNet EX2 GMP RM/PC 3700 Series Product Specifications Product Specifications Overview GMP (“Good Manufacturing Practice”) is a set of guidelines for assuring the quality of production processes in controlled industries and closely follow the guidelines issued by the European Commission or the FDA in the US. GMP applications are typically used in the pharmaceutical and food industries.
Page 18
VisuNet EX2 GMP RM/PC 3700 Series Product Specifications The VisuNet GMP product family guarantees a perfect fit for every system infrastructure. Four models are available depending on the functions required, the display and input unit and the distance over which the data is transferred. This manual describes the following two models: The remote monitor automatically connects to The complete panel PC system has many the host using RDP, or VNC, enabling via the...
VisuNet EX2 GMP RM/PC 3700 Series Product Specifications VisuNet EX2 GMP PC3719 VisuNet EX2 GMP RM3719 Connection X4: 1 ... 4 X4: 1 ... 4 X4: 5 ... 8 X4: 5 ... 8 Voltage U 4.95 V 4.95 V Current 234 mA 234 mA Power P...
Page 22
VisuNet EX2 GMP RM/PC 3700 Series Product Specifications VisuNet EX2 GMP PC3721 VisuNet EX2 GMP RM3721 Indicators/operating means Display Type TFT, LCD TFT, LCD Screen diagonal 54.6 cm (21.5 inch) 54.6 cm (21.5 inch) Resolution 1920 x 1080 Pixel 1920 x 1080 Pixel Color depth 16.7 Mio.
Page 23
VisuNet EX2 GMP RM/PC 3700 Series Product Specifications VisuNet EX2 GMP PC3721 VisuNet EX2 GMP RM3721 Data for application in connection with Ex-areas Touchscreen II 3G Ex ic ec nC [ic] IIC T4 Gc Non-Touchscreen II 3G Ex ic ec [ic] IIC T4 Gc All units II 3D Ex ic tc [ic] IIIC T85°C Dc Certificate of conformity...
VisuNet EX2 GMP RM/PC 3700 Series Product Specifications VisuNet EX2 GMP PC3721 VisuNet EX2 GMP RM3721 Power P 1582 mW 1582 mW Characteristic curve trapezoid trapezoid Internal resistor 33.2 33.2 Lumped capacitances AND = 14 µF L = 5 µH = 14 µF L = 5 µH inductances...
Page 25
VisuNet EX2 GMP RM/PC 3700 Series Product Specifications VisuNet EX2 GMP PC3722 VisuNet EX2 GMP RM3722 Interface Interface type 1 x Ethernet (Ex ec) , 3 x USB 1 x Ethernet (Ex ec) , 3 x USB (Ex ic) , 1 x RS 485 (Ex ec) , 1 (Ex ic) , 1 x RS 232 (Ex ec) , 1 x USB (Ex ec), 1 x TTY x USB (Ex ec), 1 x TTY...
Page 26
VisuNet EX2 GMP RM/PC 3700 Series Product Specifications VisuNet EX2 GMP PC3722 VisuNet EX2 GMP RM3722 Rated current 400 mA 400 mA Maximum safe voltage U 60 V 60 V Interface type 2 Serial interface RS 485 Serial interface RS 232 (Ex (Ex ec) Connection X3: 1 ...
VisuNet EX2 GMP RM/PC 3700 Series Product Specifications Note to technical data Note! The rear panel must be mounted to leave room for heat discharge; otherwise, the permitted temperature range and the lifespan of the device will be reduced. Make sure that the rear panel is not covered. Mount the housing with a minimum distance of 10 cm from the wall.
VisuNet EX2 GMP RM/PC 3700 Series Product Specifications EX2 mounting bracket Devices of type VisuNet Ex2 GMP always consist of 2 units: 1. VisuNet Ex2 GMP basic unit (display) 2. EX2 mounting bracket Danger! Danger of explosion Substantial material damage, personal injury even up to death Only VisuNet EX2 GMP basic units (displays) with proper mounted EX2 mounting brackets are allowed to be used in hazardous areas (zone 2/22).
VisuNet EX2 GMP RM/PC 3700 Series Product Specifications 2.8.1 Interfaces and pin assignment The interfaces of the VisuNet EX2 GMP PC/RM are located within the EX2 mounting bracket at the back of the housing. Power Supply Ex ec Ethernet RS232/RS485 (Com 3) Ex ec USB Ex ec USB Ex ic (mouse/keyboard) USB Ex ic (mouse/keyboard)
Page 30
VisuNet EX2 GMP RM/PC 3700 Series Product Specifications Connection Layout Cable Color brown/white brown X3 - RS232/RS485 (Com 3) Ex ec* / USB Ex ec RM (RS232) PC (RS485) Com 1 nA: Rx Com 1 nA: Tx Com 1 nA: GND n.c.
VisuNet EX2 GMP RM/PC 3700 Series Product Specifications Connecting DATL-A4-0,50-3 to VisuNet EX2 mouting bracket DATL-A4-0,50-3 VisuNet EX2 VisuNet EX2 colour Connecting pin X5 Connecting X5 signal grey yellow blue Accessories The following accessories are available. 2.9.1 Keyboards There are several keyboard models available. All keyboard foils have an antibacterial coating. For this reason the keyboards are perfectly suitable for environments with high hygienic standards.
Page 33
VisuNet EX2 GMP RM/PC 3700 Series Product Specifications EXTA3-K3 Electromagnetic compatibility 2014/30/EU EN 61326-1:2013 Conformity Degree of protection IP65 , if trackball is inactive. Undefined during motion. Ambient conditions Ambient temperature 0 ... 50 °C (32 ... 122 °F) Storage temperature -20 ...
Page 34
VisuNet EX2 GMP RM/PC 3700 Series Product Specifications EXTA3-K4 General specifications Type Keyboard with touchpad Supply Rated voltage Ex i, via data line Indicators/operating means Keyboard 105 short stroke keys Keyboard layout: US international, German, French, (further keyboard layouts on demand) Touchpad Active Principle capacitive...
Page 35
VisuNet EX2 GMP RM/PC 3700 Series Product Specifications Keyboard EXTA3-K6 Keyboard with joystick for controlling the mouse pointer. 2 separate buttons below the joystick assume the function of left and right mouse button. EXTA3-K6 General specifications Type Keyboard with joystick Supply Rated voltage Ex i, via data line...
VisuNet EX2 GMP RM/PC 3700 Series Product Specifications EXTA3-K6 Group, category, type of protection II 3G Ex ic IIC T4 Gc II 3D Ex ic IIIB T135°C Dc Certificate of conformity PF 11 CERT 1918 X Input Voltage Ui 5.4 V Current Ii 240 mA Power Pi...
VisuNet EX2 GMP RM/PC 3700 Series Product Specifications 2.9.3 Hole pattern of the turnable pedestal Mounting version turnable, fastening at front: Angle of turn for turnable mounting version The first stop plate is premounted for a max. angle of turn of 350°. With the second enclosed stop plate you can define an individual angle.
VisuNet EX2 GMP RM/PC 3700 Series Product Specifications Mounting version turnable, fastening at front: Figure 2.8 Turnable mounting version 1. Locking screw 2. premounted stop plate Angle of turn for turnable mounting version The first stop plate is premounted for a max. angle of turn of 350°. With the second enclosed stop plate you can define an individual angle.
VisuNet EX2 GMP RM/PC 3700 Series Product Specifications Model Number Description DATL-A2-4.0N/2.5F-2 Power cable 2x 4.0mm² +2.5m 2.5mm², wire end ferrule, length: 110 m DATL-A2-2.5-1 Power cable 2x 2.5mm², wire end ferrule, max. length 80 m Network Model Number Description SK-FX-100-1-8 Switch for safe area DIN rail mounting, power supply 9-24 V DC,...
Page 41
VisuNet EX2 GMP RM/PC 3700 Series Product Specifications Order designation wireless barcode system Device Order designation Description PSCAN-M PSCAN-M-1V-C2-EU- Wireless handheld barcode reader with display 10-N ATEX II 2G, Ex ib [op is] IIB T4 Gb 433 MHz PSCAN-B PSCAN-B-C2-EU-20- Base station A-10-N ATEX II 2G Ex ib IIB T4 Gb...
Page 42
VisuNet EX2 GMP RM/PC 3700 Series Product Specifications Dimensions VisuNet EX2 GMP with holder for handheld barcode reader Dimensions VisuNet EX2 GMP RM/PC 3719 (in mm) 29,3 Figure 2.11 Dimensions VisuNet EX2 GMP RM/PC 3719 Dimensions VisuNet EX2 GMP RM/PC 3721/3722 (in mm) 29,3 Figure 2.12 Dimensions VisuNet EX2 GMP RM/PC3721 and RM/PC3722...
Shielded cables improve signal quality and reduce interference and radiation of electromagnetic fields. Thus Pepperl+Fuchs recommends to use shielded data cables (RS232, USB, Ehternet). To ensure optimum signal quality the shield must be connected and grounded permanently. The following 3 shielding concepts exist: 1.
Page 45
Which of these three concepts is used must be determined by the user on a case-to-case basis (best interference suppression and safety). Pepperl+Fuchs does not accept any responsibility for choosing the right shielding concept. The "Box-A10" accessory provides a contact spring so that you can easily connect the cable shield via a DIN mounting rail to earth.
VisuNet EX2 GMP RM/PC 3700 Series Installation and Commissioning General Mounting Information Note! The following mounting requires 2 persons. Note! For fastening the pedestal, use 4 screws (M8) which suit the soil conditions. Tools required for assembly Use the follwing tools for assembly (not included in the scope of supply): Allen key, 3,5 mm, 3 mm, 4 mm ■...
VisuNet EX2 GMP RM/PC 3700 Series Installation and Commissioning Figure 3.1 Ground connection (3) on cable gland plate Cable gland M12 Cable gland M25 Ground connection Cable gland M16 Factory-mounted it's a 4 mm cable between ground connection at pedestal and the ground connection on the cable gland plate.
VisuNet EX2 GMP RM/PC 3700 Series Installation and Commissioning Grounding VisuNet GMP at pedestal Note! Depending on the grounding cable you need the adequate cable lug (not included in delivery). 1. Insert the grounding cable into the cable lug (7). 2.
Page 49
VisuNet EX2 GMP RM/PC 3700 Series Installation and Commissioning 1. To seal the pedestal against the floor, use the enclosed gasket. 2. Mount the pedestal by using the 4 screws (M8). Figure 3.4 Pedestal from bottom (photo) and from side (drawing) 1.
Page 50
VisuNet EX2 GMP RM/PC 3700 Series Installation and Commissioning 2. Remove the cable gland plate inside the EX2 wall bracket by unscrewing the 4 screws. Running the keyboard cable through the pedestal If you use a pedestal with keyboard pipe (PEDESTAL1-150-1P-KP-*), a wire pull is already installed for running the keyboard cable through the pedestal.
Page 51
VisuNet EX2 GMP RM/PC 3700 Series Installation and Commissioning Running cables through pedestal For easier installation of the connection cables through the pedestal, wires are already installed through the pedestal and the cable glands (1). 1. Depending on cable diameter, choose the adequate cable gland (e.g. 1 cable gland for sup- ply cable, 1 cable gland for network cable).
Page 52
VisuNet EX2 GMP RM/PC 3700 Series Installation and Commissioning Connecting Cable to VisuNet Ex2 GMP Danger! Danger of explosion Substantial material damage, personal injury or even up to death Before connecting or disconnecting the device must be disconnected from power supply. The bigger, upper area of the EX2 mounting bracket is defined as Ex nA.
Page 53
VisuNet EX2 GMP RM/PC 3700 Series Installation and Commissioning 3. Tighten the cable glands. 4. Attach the cable gland plate to the EX2 wall bracket (Torque 3 Nm). Make sure you pull back the cables into the pedestal resp. into the space below the EX2 wall bracket.
Page 54
VisuNet EX2 GMP RM/PC 3700 Series Installation and Commissioning Content of the cable mounting set (included in delivery) 5 x plug (X1 to X5) ■ 2 x cable tie ■ 6 x silicon tube ■ Connecting Cable to VisuNet EX2 GMP Danger! Danger of explosion Substantial material damage, personal injury or even up to death...
Page 55
VisuNet EX2 GMP RM/PC 3700 Series Installation and Commissioning 1. Screw the cable glands with a fork wrench 2. To plug up cable glands that are not in use lightly tighten the cable gland. 3. Plug the caps in. Sealing the cable gland with a cap 4.
VisuNet EX2 GMP RM/PC 3700 Series Appendix Appendix Chemical resistance of keyboard foil The keyboard foil is manufactured from a biaxially aligned polyester-based material and therefore has a greater restistance to solvents. The foil is stronger and more durable than other standard foils used on keyboards and front panels, such as polycarbonate and PVC.
Page 60
VisuNet EX2 GMP RM/PC 3700 Series Appendix Tetrahydrofuran ■ Slight discoloration Intense examinations established that the following products caused slight discoloration: Mustard ■ Tomato juice ■ Tomato ketchup ■ Lemon juice ■ ■ Coffee ■ Note! Various other substances may cause the surface structure to alter. Testing and subsequent assessment still require clarification.
Page 61
VisuNet EX2 GMP RM/PC 3700 Series Appendix 5. Remove the keyboard and put it out of the front housing. 4.5.2 Attach the keyboard EXTA3-K* Attach the keyboard 1. Remove the cover plate of the keyboard. 2. Replace the 8x distance bolts to 8x lock nuts. Tighten the lock nuts, torque 0,3 Nm. 3.
Page 62
VisuNet EX2 GMP RM/PC 3700 Series Appendix Lock washer M3 Washer M3 Washer M4 Toothed lock washer M4 8. Put the cable into the board. 9. Close the bottom plate. 10.To ensure compatibility with GMP requirements, the gap present between keyboard perimeter and enclosure must be filled with silicone bead.
Page 63
VisuNet EX2 GMP RM/PC 3700 Series Appendix This page left blank intentionally.
Page 64
PROCESS AUTOMATION – PROTECTING YOUR PROCESS Worldwide Headquarters Pepperl+Fuchs GmbH 68307 Mannheim · Germany Tel. +49 621 776-0 E-mail: info@de.pepperl-fuchs.com For the Pepperl+Fuchs representative closest to you check www.pepperl-fuchs.com/contact www.pepperl-fuchs.com Subject to modifications DOCT-2179M Copyright PEPPERL+FUCHS • Printed in Germany 07/2018...
Need help?
Do you have a question about the VisuNet EX2 GMP RM/PC 3700 Series and is the answer not in the manual?
Questions and answers