VisuNet EX2 GMP RM/PC 3700 Series
Installation and Commissioning
Content of the cable mounting set (included in delivery)
5 x plug (X1 to X5)
2 x cable tie
6 x silicon tube
Connecting Cable to VisuNet EX2 GMP
Danger!
Danger of explosion
Substantial material damage, personal injury or even up to death
All cables containing intrinsically safe and non intrinsically safe circuits must be isolated
between themself sufficently. Use the supplied silicon tubs for this. Fix the cables that they
cannot touch the walls. Use the supplied cable ties for this.
1. For additional insulation of the cables silicon tubs are provided. Adjust the silicon tubs (elec-
trical strength > 2 kV) according to the required length. Insert every connecting cable if nec-
essary with the marking flags through the silicon tubs. Connect the connection cables to the
according plugs (included in delivery). Make sure the network cable is twisted up to the plug.
Figure 3.5
2. Connect the plugs to the sockets and screw the plugs to the device.
3. Secure all cables with cable ties so that a fixed installation is guaranteed. Avoid the contact
between the cables and the walls.
4. Close the cover (torque 1,6 Nm). Use screws with seals.
Tightening/Sealing the cable glands
Danger!
Danger of explosion
Substantial material damage, personal injury or even up to death
Tighten the cable glands correct. Sealing the cable glands with a caps..
54
Example of cable mounting

Advertisement

Table of Contents
loading