Parameters
Note
Motor data
For optimum torque control during the stopping procedure, enter the motor data of the motor
connected to the soft starter in the selected parameter set using the "Motor parameters"
menu item. The "Motor parameters" menu item can be found at the following path:
"Parameters > Soft Starter > Motor parameters".
Parameters
Stopping time
Stopping torque
SIRIUS 3RW55 soft starter
Manual, 08/2018, A5E35630887002A/RS-AB/002
Description
The length of the stopping time defines the time within which the
motor voltage is reduced from line voltage to 0 V.
It may take longer for the motor to actually coast down to a
standstill.
The parameter value "0" causes the motor to be shut down
immediately without a down ramp.
Factory setting: 10 s
Setting range: 0 ... 360 s
Increment: 0.1 s
The motor torque is "controlled" until the stopping torque is
reached and then switched off.
Factory setting: 10 %
Setting range: 10 ... 100 %
Increment: 5%
Functions
7.3 Run-down
99