Siemens SIRIUS 3RW55 Manual page 123

Soft starters and solid-state switching devices
Hide thumbs Also See for SIRIUS 3RW55:
Table of Contents

Advertisement

Parameters
Parameters
Switching frequency monitoring
Maximum number of starts
Switching frequency monitoring time t
Switching frequency monitoring time t
Response to ON-command during active
monit. time
SIRIUS 3RW55 soft starter
Manual, 08/2018, A5E35630887002A/RS-AB/002
Description
Deactivated (factory setting)
The switching frequency monitoring is deactivated.
Mode 1 (ON-ON)
The switching frequency monitoring always relates to the start time of the
preceding Motor ON command and the start time of the new Motor ON
command. The switching frequency monitoring time t
as an effective switch-on command is present.
Mode 2 (OFF-ON)
The switching frequency monitoring always relates to the end time of the
preceding Motor ON command (Motor OFF) and the starting time of the
new Motor ON command. The switching frequency monitoring time t
starts as soon as no effective switch-on command is present.
This parameter is only relevant in combination with the switching frequency
monitoring time t
time t
has the value "0" (= deactivated), then this parameter is irrelevant
2
and its value has no meaning.
If the parameter for the switching frequency monitoring time t
not equal to "0" (= activated), then this parameter defines the maximum
number of starts, until which the switching frequency monitoring time t
does not have to be observed. At the latest upon reaching the maximum
number of starts, the switching frequency monitoring time t
observed once. If the switching frequency monitoring time t
before reaching the maximum number of starts, then the counter for the
number of starts begins again at "1".
Factory setting: 2
Setting range: 2 ... 255
Increment: 1
The time t
must be shorter than the time t
1
1
The parameter value "0" deactivates the switching frequency monitoring
time t
.
1
Factory setting: 0 s
Setting range: 0 ... 65 535 s
Increment: 1 s
The time t
must be longer than the time t
2
2
The parameter value "0" deactivates the switching frequency monitoring
time t
.
2
Factory setting: 0 s
Setting range: 0 ... 65 535 s
Increment: 1 s
Trip with restart
The trip is automatically acknowledged if no monitoring time is still active.
If an ON command is still pending, the motor is switched on.
Trip without restart
The trip must be acknowledged with the "Reset" function.
. If the parameter for the switching frequency monitoring
2
1.
Functions
7.7 Condition Monitoring
or t
starts as soon
1
2
has a value
2
must be
2
is observed
2
.
2
or t
1
2
2
123