Functions
7.8 Asymmetry
Parameters
Parameters
Pump cleaning - mode
Pump cleaning - time
Pump cleaning - cycles
Pump cleaning - start/stop
parameters
128
Description
Deactivated (factory setting)
The pump cleaning function is deactivated.
Manual
The pump cleaning function is started with the aid of a control
command by means of an input action at the digital input or in the
process image outputs.
During the cleaning time, the pump runs at reduced speed and
the maximum possible torque.
Factory setting: 20 s
Setting range: 1 ... 30 s
Increment: 1 s
During a cycle, the pump rotation changes direction several
times.
Factory setting: 3
Setting range: 1 ... 10
Increment: 1
You can select the parameters for starting and stopping the pump
for different cleaning processes here. For example, you can make
different settings for starting and stopping in parameter set 2 than
for the normal starting and stopping procedure.
Parameter set 1
The pump cleaning function is carried out with the starting and
ramp-down parameters of parameter set 1.
Parameter set 2
The pump cleaning function is carried out with the starting and
ramp-down parameters of parameter set 2.
Parameter set 3
The pump cleaning function is carried out with the starting and
ramp-down parameters of parameter set 3.
Operating parameters (factory setting)
The pump cleaning function is carried out with the starting and
ramp-down parameters of the currently selected parameter set.