Messages and diagnostics
8.4 Faults and remedial actions of the 3RW55 soft starter
Faults
Asymmetry tripping
Above threshold I
Below threshold I
Current fault limit disconnection
Ground fault
Electronics supply voltage too low
Bus error
Process image error
Parameter fault
Missing startup parameters
Device error
Module slot wrong or configuration
faulty
Motor connection variant unknown
or incorrect
Zero current after ON command
Phase failure
L1
L2
L3
Overvoltage
Bypass defective
180
Cause
Additional tripping in the case of asymmetry
The current has exceeded a limit.
The current has undershot a limit.
Additional tripping in the event of a current
fault limit overshoot or undershoot.
The ground-fault monitoring has responded.
An impermissibly high residual current is
flowing.
The supply voltage is below the permitted
value.
Fault in the fieldbus communication.
You will find further information in the manual
for the 3RW5 communication module in
question.
The process image output (PIQ) contains
invalid control bit combinations (e.g. control
bits for clockwise and counter-clockwise
rotation are set at the same time).
The module is not or is incorrectly
parameterized or parameterization changes
are denied in current operating mode.
Necessary startup data for the device are
missing.
Unrecoverable error detected after internal
diagnostics (self-test, contactor contacts,
switching element, etc.).
Real and configured slot of module is
different.
The motor connection variant was not
recognized or is different from configuration.
No current flow is detected after the motor
feeder is switched on. Possible causes:
Main circuit interrupted (fuse, circuit
breaker)
Motor contactor or contactor control is
defective
The parameter execution time is too short
No load
The main power monitoring detects a phase
failure.
The supply voltage is above the tolerance
limit.
-
Remedy
-
Check the application driven by the
motor.
-
Check the connecting cable of the
motor for damage.
Check the power supply (load rating,
voltage range).
-
Check and correct the process image
output (PIQ).
Correct and execute
parameterization.
Switch the operating mode and
repeat parameterization.
Check parameterization or startup data
records.
Replace the device.
Ensure consistency between plugged
and configured module.
Ensure correct connection.
-
-
Change the power supply.
Check bypasses for L1, L2 and L3 and
replace defective bypasses.
SIRIUS 3RW55 soft starter
Manual, 08/2018, A5E35630887002A/RS-AB/002