Drive Parameters - Omron Q2A-A Series Installation & Operation Instructions

200 v class 0.55 kw to 110 kw, 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A-A Series:
Table of Contents

Advertisement

1 English
Terminal
DI1-DI8, DIC, D0V, D24V
H1, H2, HC
PI, +10V, -10V, AI1, AI2, AI3, A0V
PO, AO1, AO2, A0V
RS485+, RS485-, A0V
1NO, 1NC, 1CM, 2NO, 2CM, 3NO, 3CM, 4NO,
4CM
E24V, GND
Crimp Ferrules
Attach an insulated sleeve to the wire when connecting crimp ferrules. We recommend the CRIMPFOX 6
crimping tool from PHOENIX CONTACT.
Wire Gauge
mm
2
(AWG)
0.25 (24)
0.34 (22)
0.5 (20)
Drive Start-Up
Setup Wizard
Refer to the motor nameplate and record the information in this table before you start the drive.
Item
Motor Rated Power
Motor Rated Voltage
Motor Rated Current
Motor Rated Frequency
Open the clock battery cover to put in a battery to use the clock functions. Select a type CR2016 battery with a
nominal voltage of 3 V.

Drive Parameters

Refer to the following table when setting the most important parameters.
Note:
You can change parameters with "RUN" in the "No." column during Run.
No.
(Hex.)
A1-00
Language Selection
(0100)
RUN
A1-03
Init Parameters
(0103)
EN 10
Table 1.3 Wire Gauges
Recommended Gauge
mm
2
(AWG)
0.75
(18)
Figure 1.3 Crimp Ferrule Dimensions
Table 1.4 Crimp Ferrule Models and Dimensions
Model
L (mm)
AI 0.25-8YE
12.5
AI 0.34-8TQ
12.5
AI 0.5-8WH,
14
AI 0.5-8OG
Value
Name
Sets the language for the LCD keypad.
0: English, 1: Japanese, 2: German, 3: French, 4: Italian, 5: Spanish, 6: Portuguese, 7: Chinese, 8: Czech, 9: Russian,
10: Turkish, 11: Polish, 12: Greek
Sets parameters to default values.
0: No Initialization, 1110: User / Solution Initialization, 2220: 2-Wire Initialization, 3330: 3-Wire Initialization,
4440: Q2pack Init
Bare Wire
Applicable Gauge
mm
2
(AWG)
• Stranded wire
0.2 to 1.0
(24 to 18)
• Solid wire
0.2 to 1.5
(24 to 16)
L1 (mm)
8
8
8
Item
kW
Motor Maximum Frequency
V
Number of Motor Poles
A
Motor Base Rotation Speed
Hz
Number of Motor Encoder Pulses
Description
TOMPYEUOQ2A03B AC Drive Q2A Installation and Operation Instructions
Crimp Ferrule
Recommended Gauge
Applicable Gauge
mm
2
(AWG)
mm
0.5
(20)
d1 (mm)
0.8
0.8
1.1
Value
2
(AWG)
0.25 to 0.5
(24 to 20)
d2 (mm)
2.0
2.0
2.5
Hz
min
-1
(r/min)
ppr

Advertisement

Table of Contents
loading