Omron Q2A-A Series Installation & Operation Instructions page 12

200 v class 0.55 kw to 110 kw, 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A-A Series:
Table of Contents

Advertisement

1 English
No.
(Hex.)
H2-03
4NO-4CM Funct Selection
(040D)
H3-01
AI1 Signal Level Select
(0410)
H3-02
AI1 Function Selection
(0434)
H3-03
AI1 Gain Setting
(0411)
RUN
H3-04
AI1 Bias Setting
(0412)
RUN
H3-05
AI3 Signal Level Select
(0413)
H3-06
AI3 Function Selection
(0414)
H3-07
AI3 Gain Setting
(0415)
RUN
H3-08
AI3 Bias Setting
(0416)
RUN
H3-09
AI2 Signal Level Select
(0417)
H3-10
AI2 Function Selection
(0418)
H3-11
AI2 Gain Setting
(0419)
RUN
H3-12
AI2 Bias Setting
(041A)
RUN
H3-13
An.In FilterTime Constant
(041B)
H3-14
An.In Term.Enable Sel
(041C)
H4-01
AO1 An.Out Select
(041D)
H4-02
AO1 An.Out Gain
(041E)
RUN
H4-03
AO1 An.Out Bias
(041F)
RUN
H4-04
AO2 An.Out Select
(0420)
H4-05
AO2 An.Out Gain
(0421)
RUN
H4-06
AO2 An.Out Bias
(0422)
RUN
H4-07
AO1 Signal Level Select
(0423)
H4-08
AO2 Signal Level Select
(0424)
L1-01
Motor Cool Type for OL1 Calc
(0480)
EN 12
Name
Sets the function for MFDO terminal 4NO-4CM.
Sets the input signal level for MFAI terminal AI1.
0: 0 to 10V (Lower Limit at 0), 1: -10 to +10V (Bipolar Reference), 2: 4 to 20 mA, 3: 0 to 20 mA
Sets a function for MFAI terminal AI1.
Sets the gain of the analog signal input to MFAI terminal AI1.
Sets the bias of the analog signal input to MFAI terminal AI1.
Sets the input signal level for MFAI terminal AI3.
0: 0 to 10V (Lower Limit at 0), 1: -10 to +10V (Bipolar Reference), 2: 4 to 20 mA, 3: 0 to 20 mA
Sets a function for MFAI terminal AI3.
Sets the gain of the analog signal input to MFAI terminal AI3.
Sets the bias of the analog signal input to MFAI terminal AI3.
Sets the input signal level for MFAI terminal AI2.
0: 0 to 10V (Lower Limit at 0), 1: -10 to +10V (Bipolar Reference), 2: 4 to 20 mA, 3: 0 to 20 mA
Sets a function for MFAI terminal AI2.
Sets the gain of the analog signal input to MFAI terminal AI2.
Sets the bias of the analog signal input to MFAI terminal AI2.
Sets the time constant to apply a primary delay filter to the MFAI terminal.
Sets the enabled terminal or terminals when H1-xx: MFDI Function Select = 12 [AI Input Sel] is ON.
1: AI1 only, 2: AI2 only, 3: AI1 and AI2, 4: AI3 only, 5: AI1 and AI3, 6: AI2 and AI3, 7: AI1, AI2, and AI3
Sets the monitor number to send from MFAO terminal AO1.
Sets the gain of the monitor signal that is sent from MFAO terminal AO1.
Sets the bias of the monitor signal that is sent from MFAO terminal AO1.
Sets the monitoring number to be output from the MFAO terminal AO2.
Sets the gain of the monitor signal that is sent from MFAO terminal AO2.
Sets the bias of the monitor signal that is sent from MFAO terminal AO2.
Sets the MFAO terminal AO1 output signal level.
1: 0 to 10 Vdc, 2: -10 to +10 Vdc, 3: 4 to 20 mA
Sets the MFAO terminal AO2 output signal level.
1: 0 to 10 Vdc, 2: -10 to +10 Vdc, 3: 4 to 20 mA
Sets the motor overload protection with electronic thermal protectors.
0: Disabled, 1: VTorque, 2: CT 10:1 Speed Range, 3: CT 100:1 SpeedRange, 4: PM VTorque, 5: PM CTorque,
6: VT (50Hz)
Description
TOMPYEUOQ2A03B AC Drive Q2A Installation and Operation Instructions