Command 205: Get Flame Device Info - MSA FL500 UV/IR Operating Manual

Hart communication
Hide thumbs Also See for FL500 UV/IR:
Table of Contents

Advertisement

Device-specific Commands

9.27. Command 205: Get Flame Device Info

Request Data Bytes
Byte
Format
None
N/A
Response Data Bytes
Byte
Format
0-1
Unsigned-16
2-3
Unsigned-16
4-5
Unsigned-16
6-7
Unsigned-16
8-9
Unsigned-16
10-11 Unsigned-16
12-13 Unsigned-16
14-15 Unsigned-16
16-17 Unsigned-16
18-19 Unsigned-16
20-21 Unsigned-16
22-23 Unsigned-16
Command-specific Response Codes
Code
Class
0
Success
US
1-127
30
Description
N/A
Description
UV signal counts
UV COPM Fault count
IR1 signal count
IR1 COPM Fault count
IR amplitude in millivolts (mV)
IR maximum in mV
IR minimum in mV
Reserved
Reserved
Reserved
Reserved
Reserved
Description
No command-specific errors
Undefined
FL500 HART® Communication Operating Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents