Overload detect
CD67
0 : Normal
1 : Overload detection and stop
Motor stops operation if load condition is reached CD68 and CD69
setting.
2 : Two stages overload detection and stop (CD68<100% only).
AC drive will limit output current at CD68 setting if load condition is
reached CD68 and CD69 setting. And motor will stop operation if
timing of limited output current is reached CD70 setting.
Overload setting
CD68
Set overload level.
Overload time
setting
CD69
Set overload time.
2nd stage overload
time setting
CD70
Set 2nd stage overload time.
Setting Range
Default Value
Setting Range
Default Value
Setting Range
Default Value
Setting Range
Default Value
51
0 ~ 2
0
20.0 ~ 200.0%
150.0%
0.0 ~ 60.0SEC
60.0SEC
0.0 ~ 120.0SEC
20.0SEC