Page 1
ADLEEPOWER INSTRUCTION MANUAL GENERAL-PURPOSE INVERTER MS2 / MS4 THANK YOU VERY MUCH FOR YOUR PURCHASE OF ADLEE INVERTER MS SERIES. PLEASE READ THIS INSTRUCTION MANUAL BEFORE INSTALLATION OF THE INVERTER.
Page 2
PREFACE This general-purpose inverter made by ADLEE Powertronic., Ltd. Read this instruction manual throughly before operation. This manual will be helpful in the installation, parameter setting, trouble- shooting, and daily maintenance of the AC motor drives. To guarantee safe operation of the equipment, read the following safety guidelines before connecting power to the AC drives.
Page 3
RECEIVING CAUTION * Do not install or operate the driver which is damaged or has missing parts. Failure to observe this caution may result in personal injury or equipment damage. INSTALLATION CAUTION * Lift the cabinet by the base. When moving the unit, never lift by the front cover.
Page 4
CAUTION * Verify that the driver rated voltage coincides with the AC power supply voltage. Failure to observe this caution can result in personal injury or a fire. * Do not perform a withstand voltage test of the driver. It may cause semi-conductor elements to be damaged. * To connect a braking resistor, follow in APPENDIX A.
Page 5
CAUTION * Since it is easy to change. operation speed from low to high speed, verify the safe working range of the motor and machine before op- eration. Failure to observe this caution can result in personal injury and machine damage. * Do not change signals during operation.
Page 6
CAUTION * The control PC board employs CMOS ICs. Do not touch the CMOS elements by hand. They are easily damaged by static electricity. * Do not connect or disconnect wires or connectors while power is applied to the circuit. Failure to observe this caution can result in personal injury.
1. RECEIVING This MS series AC drive has gone through rigorous quality control tests at the factory before shipment. After receiving the AC drive, please check for the following : (1) No damage is found on each product after shipping.
2. SPECIFICATIONS Model Voltage 1 110VAC 10% ψ 220VAC ± ± ψ Model No MS1-104 MS2-102 MS2-104 MS2-107 MS2-115 MS2-122 MS2-137 Input Frequency 50HZ ~ 60HZ ± Output Voltage 110VAC 220VAC ψ ψ Output Frequency 0.5 ~ 1200HZ Output 4.1 A 1.4 A 2.5 A 4.1 A...
Page 10
Model Voltage ψ 380/440VAC ± Model No MS4-307 MS4-315 MS4-322 MS4-337 Input Frequency 50HZ ~ 60HZ ± Output Voltage ψ 380/440VAC Output Frequency 0.5 ~ 1200HZ Output 2.5 A Rated current (A) Capacity (KVA) 1.9 KVA 3.1 KVA 4.2 KVA 6.9 KVA Largest motor 0.75 KW...
4. INSTALLATION Inadequate environment around installation site and installation surface can result in damage to the inverter. Before operating the MS series inverter, please check the following points : (1) Avoid high temperature, high humidity, easy-to-dew ambient envi- ronment. Don’ t expose to dust or dirt, corrosive gas, and coolant mist, and direct sunlight.
5. DESCRIPTION OF TERMINALS (1) Main circuit connection diagram MS1-104, MS2-102~122 L1 L2 U 60 80W Ω GROUND External braking resistor POWER Refer to the appendix A MOTOR SOURCE MS2-307~322, MS4-307~322 L1 L2 L3 U 180 80W Ω GROUND External braking resistor Refer to the appendix A MOTOR POWER...
Page 17
MS2(4)-337 L2 L3 U P PR MS2-337 60 80W : Ω MS4-337 180 80W : Ω GROUND External braking resistor Refer to the appendix A MOTOR POWER SOURCE Main circuit terminal Symbol Description Terminal name Ground Ground(Earth) Terminal (L1,L2) Single Phase (L1,L2,L3) Three Phase 110VAC±...
Page 18
(2) Control circuit terminal MS1-104, MS2-102~137, MS4-337 MA CF3 MC A/B C VCC FA1 GNDFWD REV FT1 FT2 MT COM Fault Relay Contact rating 1A 240VAC 1A 30VDC MS4-307~322 VCC FA1 2-4 2-5 VR5KB 1-1 1-2 1-4 1-5 1-7 1-8 FT2 COM FWD REV FWD REV...
Page 19
Running relay terminal Symbol Terminal name Description Running signal A Running contact (normal open) Running signal B / multi- Running contact (normal close) / 5-8th function terminal speed terminal Running signal C Running contact (common) Alarm terminal Symbol Terminal name Description Fault alarm contact A(normal open) / Alarm output B...
Page 21
4-1 Jumper setup-MS1-104, MS2-102~122 1. JP1 : VR on panel / VR on F306 VR on panel VR on F306 2. S1 : MB / CF3 selection 2 and 3 short CF3→ 1 and 2 short CF3 → Running relay MB 5-8th speed terminal (Refer Example 04) 3.
Page 22
Jumper setup-MS4-307~322 1. JP1 : VR on panel / VR on F306 VR on panel VR on F306 2. S1 : MB / CF3 selection 2 and 3 short CF3→ 1 and 2 short CF3 → Running relay MB 5-8th speed terminal (Refer Example 04) 3.
Page 23
Jumper setup-MS2-137, MS4-337 1. JP1 : VR on panel / VR on F306 VR on panel VR on F306 2. S1 : MB / CF3 selection 2 and 3 short CF3→ 1 and 2 short CF3 → Running relay MB 5-8th speed terminal (Refer Example 04) 3.
Page 24
(5) WIRING MS2-Series 5-1 Wiring of main circuit THRY MCCB Filter 5-2 Wiring equipments Select the wiring equipment and wiring size, refer to the table below. 1. On the input power side, a molded case circuit breaker (MCCB) to protect inverter primary wiring should be installed. 2.
Page 25
5-3 Surge absorber In order to prevent malfunction, provide the surge absorber on the coils of the electromagnetic contactors, relays and other devices which are to be used adjacent of the inverter. 5-4 Cable size and length If the inverter is connected to a distant motor (especially when low frequency is output), motor torque decreases because of voltage drop in the cable.
Page 26
B. Control signal circuit 1. Separate the power cables of main circuit etc. from the control cables of the sequence and analog signals by passing the cables through the different ducts. 2. Use twisted pair shielded wire for control signal and connect the shield to earth terminal at on end, COMMON terminal of control board.
6. DIGITAL OPERATION PANEL LED Operating MS2- Model Indication Indication Digital Indication FUNC CHARGE LED Operating Indication F306 Digital Indication PROG STOP REMOTE CONTROL FUNC STOP Operation key Key function Description FWD RUN Forward run Commands forward run REV RUN Reverse run Commands reverse run Cursor...
7. FUNCTIONS DESCRIPTION DISPLAY FUNCTION DEFAULT VALUE CODE 60.0HZ CD00 First speed setting ☆ 50.0HZ CD01 Parameter lock CD02 Acceleration time 1 10.0Sec CD03 Deceleration time 1 10.0Sec CD04 Jogging frequency 5.0HZ CD05 Start frequency 0.5HZ CD06 Jog mode 120.0 CD07 Analog output gain ☆...
Page 29
ADJUST USER UNIT REMARK RANGE SETTING 60HZ region 0.0 ~ 1200HZ 0.1HZ 50HZ region 0 or 1 0 = lock 1 = Unlock 0.1 ~ 6000.0Sec 0.1Sec 0.1 ~ 6000.0Sec 0.1Sec 0.0 ~ 1200HZ 0.1HZ 0.5 ~ 30.0HZ 0.1HZ 0 or 1 0 = Normal 1 = Jog 60HZ region 30.0 ~ 1200HZ...
Page 30
DISPLAY FUNCTION DEFAULT VALUE CODE CD18 V/F pattern setting CD19 DC braking time 1.0Sec CD20 DC braking power CD21 Torque boost 0.0% CD22 Second speed setting 20.0HZ CD23 Third speed setting 30.0HZ CD24 Fourth speed setting 40.0HZ CD25 Acceleration time 2 10.0Sec CD26 Deceleration time 2...
Page 36
Communication address description CODE FUNCTION DEFAULT VALUE CD96 Model code CD97 Version of program Speed command for RS485 Frequency data output for RS485 Reserved Fault code for RS485 ☆ To change version see description of CD52. This function provides different standard setting values for 50/60HZ power region.
Page 37
ADJUST USER UNIT REMARK RANGE SETTING 0 ~4 0.1HZ...
Page 38
7-1. Function setting Before starting test run, check carefully the following points : (1) Be sure to connect the power supply to L1, L2, L3 (input terminals) and the motor to W.V.U. (output terminals). (Wrong connections will damage the inverter.) (2) Check that the input power supply coincide with input voltage and input phase of the inverter.
Page 39
Operating 1-1. Pannel Action : (a) Press for forward / reverse operation. Speed : (a) Using to change motor speed with 1HZ increment step. or to select the digit for quick setting and confirm by PROG Standby : (a) Press back to standby mode after trip or function STOP setting mode.
Page 40
Setting Range 0.0 ~ 1200HZ First speed setting 60HZ region 60.0HZ CD00 50HZ region 50.0HZ Press key for increase or decrease the speed. Press key to select the digit for quick setting. Press to save the setting value. PROG Parameter lock Setting Range 0 or 1 Default value...
Page 41
Deceleration time 1 Setting Range 0.1 ~ 6000.0Sec Default value 10.0Sec CD03 CD03 value corresponds to the 60HZ time of deceleration from 50/60HZ to 0. 6000 TIME(Sec) Jogging frequency Setting Range 0.0 ~ 1200HZ Default value 5.0HZ CD04 1200HZ Use terminal control refer to CD12 and CD42 setting, keyboard control refer to CD06.
Page 42
Jog mode Setting Range 0 or 1 Default value CD06 0 : Normal 1 : Jog Mode 1. Set jogging operation from key panel & LED blinking in JOG mode. Note : Refer to CD12 & CD42 for using jog mode by terminal control. Setting Range 30.0 ~ 1200HZ Frequency meter...
Page 43
Analog / Digital Setting Range 0 or 1 frequency input Default value CD10 0 : Operation frequency change by using key and confirm by PROG 1 : Operation frequency depends on the analog signal. Note : Using key to change motor speed when CD01=1, the OPE3 warning message will be indicated.
Page 44
Source operation command Setting Range 0 ~ 2 Default value CD13 0 : Normal 1 : F306 2 : RS485 communication Note : After finished this parameter setting, please repower “ON”. Maximum Setting Range 0.5 ~ 1200HZ frequency limit 60HZ region 120.0HZ CD14 50HZ region...
Page 45
Frequency display Setting Range 0.01 ~ 500.0 scale 60HZ region CD16 50HZ region 30.0 Use the following equation to calculate the mechanical shaft speed in rpm. RPM = HZ Scale setting × When RPM > 9999 display for over range warning in this condition.
Page 46
Constant power setting range 100% 0.5HZ 1200HZ Constant torque V/F pattern setting Setting Range 0 ~ 2 Default value CD18 0 = Constant torque curve Volt 100% 1 = Reduce torque curve F 2 = Reduce torque curve F 1200(Hz) DC braking time Setting Range 0.0 ~ 25.0Sec...
Page 47
DC braking power Setting Range 0 ~ 250 Default value CD20 (HZ) CD20 setting DC voltage gain various braking DC Voltage power. 25sec Torque boost Setting Range 0.0 ~ 25.0% Default value 0.0% CD21 Torque boosting is used to compensate the torque lost due to stator resistance.
Page 48
Fourth speed setting Setting Range 0.0 ~ 1200HZ Default value 40.0HZ CD24 Terminal Operation Signal order CF1 CF2 Terminal CF1 Terminal CF2 SPEED SPEED - 1 OFF OFF Output frequency SPEED - 2 ON Speed 1 Speed 1 SPEED - 3 OFF ON Speed 2 Speed 4 Speed 3...
Page 49
Carrier frequency Setting Range 1.0 ~ 15.0K Default value 15.0K CD27 Increase the carrier frequency would reduce motor noise but efficiency might be decreased. Reduce the carrier frequency would increase noise and reduce motor current, and gain better efficiency. current current Low carrier frequency High carrier frequency...
Page 50
Frequency jump 2 Setting Range 0.0 ~ 1200HZ Default value 0.0HZ CD30 Frequency jump 3 Setting Range 0.0 ~ 1200HZ Default value 0.0HZ CD31 JUMP 1 JUMP 3 JUMP 2 Speed command Jump range Setting Range 0.5 ~ 3.0HZ Default value 0.5HZ CD32 Speed command...
Page 51
Frequency Setting Range 0.0 ~ 1200HZ reference bias Default value CD33 Move Frequency bias with 100% same gradient. Frequency in the range of “-” bias, motor is stop. +Bias Analog input -Bias Freq. ref. bias direction Setting Range 0 or 1 Default value CD34 0 = Positive...
Page 52
200% (HZ) 100% Vmax Analog input The latest error record CD36 Error record 1 CD37 Error record 2 CD38 Error record 3 CD39 Errors record flow-chart when Error occur. The new content will shift the other contents to one higher CD code and the highest one will be dropped.
Page 53
Clear errors record Setting Range 0 or 1 Default value CD40 Set CD40=1 and clear CD36 ~ CD39 Error record the contents in PROG CD36 ~ CD39 are NONE “ “ HZ/RPM Display Setting Range 0 ~ 1 Default value CD41 0 = HZ Display 1 = RPM Display...
Page 54
Note : 1. Set jumper J4 and J5 to appropriate location before using FT1/FT2 functions. 2. To operate at 8 speeds function, all FT1/FT2/CF3 terminals set as FT1=CF1, FT2=CF2 and CF3=CF3. 3 - WIRE CIRCUIT CONNECTION DIAGRAM (terminal latch function) FWD(REV) COMMAND CD42=5 STOP COMMAND...
Page 55
Free analog terminal 1 Setting Range 0 ~ 15 Default value CD44 Setting Range Function Min-------Max ---------- ---------- Acceleration time 1 0 ~ CD02 Content Deceleration time 1 0 ~ CD03 Content Acceleration time 2 0 ~ CD25 Content Deceleration time 2 0 ~ CD26 Content Boost setting 0.0 ~ 25%...
Page 56
CD46=5 SPEED CF3 CF2 CF1 5th speed setting 1th speed setting OFF OFF OFF CD47 2th speed setting OFF OFF ON 3th speed setting OFF ON 6th speed setting 4th speed setting OFF ON CD48 5th speed setting ON OFF OFF 6th speed setting ON OFF ON 7th speed setting 7th speed setting...
Page 57
Dynamic braking energy limit Setting Range 0 ~ 300% Default value CD51 The higher the percentage, the more braking energy. The lower the percentage, the lower braking energy. Description of regenerative discharge braking active period. 0 : Auto-adjust 1 ~ 100% Deceleration period 101 ~ 200% Braking active period of (Decel/accel/constant frequency) 201 ~ 300% Braking active period of...
Page 58
S curve Setting Range 0 ~ 10 Default value CD53 Setting S curve non-Linear Accel/Decel Operation from 1 to 10. Setting 0 is normal operation without S curve. CD53=0 (Hz) CD53=3 CD53=7 TIME FWD RUN COMMAND REV RUN COMMAND DC injection ACCEL DECEL Braking Time Output Frequency...
Page 59
Fmax Fmin 20mA current signal Note : Refer to FA1 terminal setting for 4-20mA signal. Frequency arrive signal range Setting Range 0.0 ~ 100.0% Default value 10.0% CD55 1.Signal output at running F. setting F.x(1-CD55%) for acceleration. ≧ 2.Signal output at running F. setting F.x(1+CD55%) for deceleration.
Page 62
Auto running mode Setting Range 0 ~ 4 (Timer) Default value CD58 VALUE SPEED UNIT RANGE SPEED SETTING CD47 CD48 CD49 CD50 CD00 0 ~ 1200 TIMER SETTING CD59 CD60 CD61 CD62 CD63 0 ~ 15.00 hr.min CD12=0, use keypad to control timer CD12=0 and CD13=2, use RS485 to control timer CD12=1, CD42 or CD43=10, use FT1 or FT2 terminal to control timer Value...
Page 63
CD58=1 CD00 CD49 CD48 CD50 CD47 Time CD59 CD60 CD61 CD62 CD63 FT1/FT2 FWD/REV Section end 10ms Cycle end 10ms CD58=2 CD00 CD49 CD48 CD48 CD50 CD47 CD47 Time CD59 CD60 CD61 CD62 CD63 FT1/FT2 FWD/ Section Cycle...
Page 64
CD58=3 CD00 CD49 CD48 CD50 CD47 Time CD59 CD60 CD61 CD62 CD63 FT1/FT2 FWD/REV Section end Cycle end CD58=4 CD00 CD49 CD49 CD48 CD48 CD50 CD47 CD47 Time CD59 CD60 CD61 CD62 CD63 FT1/ FWD/ Section Cycle...
Page 65
1st step timer Setting Range 0 ~ 15 Hr Default value 0.01 Hr.min CD59 Setting running time for 1th speed.(CD47) 2st step timer Setting Range 0 ~ 15Hr Default value 0.00Hr.min CD60 Setting running time for 2th speed.(CD48) 3st step timer Setting Range 0 ~ 15Hr Default value...
Page 66
Timer unit selector Setting Range 0 ~ 1 Default value CD64 0 : hr.min 1 : min.sec Note 1 : CD64 cannot be reset to default value by CD52. Set CD64 as needs separately. Note 2 : In RS485 communication input, CD59~CD63 need to tranfer minimum unit.
Page 67
Transmission speed Setting Range 0 ~ 3 Default Value CD75 Setting the transmission speed between computer and drive. 0 : 2400 bits/second. 1 : 4800 bits/second. 2 : 9600 bits/second. 3 : 19200 bits/second. Transmission fault treatment Setting Range 0 ~ 3 Default Value CD76 0 : Alarm and keep operation.
Page 69
B. Communication protocol Data contents are in hexadecimal with postive and negative format. 1. RTU Start A silent interval of more than 10ms Address 8-bit address Function 8-bit command Data (n-1) Contents of data : n*8-bit data, n 16 ≦ Data 0 CRC CHK Low Check sum (CRCL)
Page 70
C. ASCII code description Character "0" "1" "2" "3" "4" "5" "6" "7" ASCII code 30H 31H 32H 33H 34H 35H 36H 37H Character "8" "9" "A" "B" "C" "D" "E" "F" ASCII code 38H 39H 41H 42H 43H 44H 45H 46H D.
Page 71
Example : Read two parameters of AC drive address 52(34H) from CD22. CD22=20.00(07D0H) CD23=30.00(0BB8H). 1. RTU Computer command message AC drive response message D1 Address D1 Address D2 Function D2 Function Quantity of data D3 Start address (H) (count by byte) D4 Start address (L) D4 CD22 content (H) D5 # of data (H)
Page 72
Computer command message AC drive response message # of data '0' CD23 content '0' # of data '2' CD23 content 'B' count by word '2' CD23 content 'B' CD23 content '8' D7 LRC HI LRC HI D8 LRC LO LRC LO D8 LRC HI LRC HI END HI...
Page 73
Note 3 : Processing decimal number Using following methods to process if the minimum parameter value is decimal number. Minimum unit by 1 decimal number : The original value times 10 to be a new number. Minimum unit by 2 decimal number : The original value times 100 to be a new number.
Page 74
Computer write CD00 content (60.00HZ) to inverter address=52 1. RTU Computer command message CRCL CRCH AC drive response message CRCL CRCH 2. ASCII Computer command message AC drive response message Address '3' Address '3' Address '4' Address '4' Function '0' Function '0' Function '6' Function '6'...
Page 75
Computer command message inverter address=52 foward run at 60.00HZ 1. RTU Step 1. Write CD00=60.00HZ (6000=1770H) to AC drive address=52 Computer command message CRCL CRCH AC drive response message CRCL CRCH Step 2. Write address 100 (64H)=1 Computer command message CRCL CRCH AC drive response message...
Page 76
Computer command message AC drive response message Number of parameter '0' Number of parameter '0' Number of parameter '0' Number of parameter '0' Number of parameter '0' Number of parameter '0' Number of parameter '0' Number of parameter '0' CD79 content '1' CD79 content '1' CD79 content '7' CD79 content '7'...
Page 77
Computer command message AC drive response message CD31 content '0' CD31 content '0' CD31 content '1' CD31 content '1' D7 LRC HI LRC HI D7 LRC HI LRC HI D8 LRC LO LRC LO D8 LRC LO LRC LO END HI END HI END LO END LO...
Page 78
Ex. Write data data 1=11, data 2=22, data 3=33 and data 4=44 to AC drive address 52(34H) 1. RTU Computer command message AC drive response message D1 Address D1 Address D2 Function D2 Function D3 Data 1 D3 Data 1 D4 Data 2 D4 Data 2 D5 Data 3...
Page 79
Computer command message AC drive response message D7 LRC HI LRC HI D7 LRC HI LRC HI D8 LRC LO LRC LO D8 LRC LO LRC LO END HI END HI END LO END LO CRC(Cyclical Redundancy Check) is calculated by the following steps: Step 1.
Page 80
E. Communication error respond Once communication error happened, inverter will respond “Function code and 80H” and communication error code to master system. Communication error code definition Error code Description Function code error, only 03/06/08 available Illegal data value (data value outside limit value) Illegal data address (data address is not available) Illegal operation command Check sum error...
Page 81
2. ASCII Start code Address (01) Function code & 80H (86) Error code (02) LRC (77) End code H End code L Ex. Write CD00=1500HZ(3A98H), but maximum value of CD00 is 1200HZ. 1. RTU Computer command message CRCL CRCH AC drive response message CRCL(C3H) CRCH(A1H)
Page 82
2. ASCII Computer command message AC drive response message Address '0' Address '0' Address '1' Address '1' Function '0' Function '8' Function '6' Function '6' Address content '0' Error code '0' Address content '0' Error code '2' Address content '0' LRC HI '7' Address content '0' LRC LO '7'...
Page 83
RUN terminal Setting Range 0 ~ 3 Default value CD91 ARR terminal Setting Range 0 ~ 3 Default value CD92 0 : RUN(CD46). 1 : ARR(CD55). 2 : Section ending signal : Terminal output 10ms long signal if each speed is finished.
Page 84
Communication address description Model code CD96 To know model code, using function 03H to read address 96(06H) con- tent. Version of program CD97 To know version of program, using function 03H to read address 97(61H) content. Speed command of RS485 Setting Range 0 ~ 4 Default Value...
Page 85
Fault code for RS485 Using 03H function to read address 103(67H) content to know the cause of fault if fault occurred. 01H : EP0 02H : PF01 03H : PF02 04H : PF03 05H : PF04 07H : OH 08H : OL 09H : EEP1 0AH : EEP2 31H : OPE1...
Page 86
7-2. Operation key-in sequence EXAMPLE : CHANGE acceleration time from 10sec to 12.3sec. Setting Display Description sequence indicator In waiting mode, the display is blinking Enter function mode FUNC Select function number 1 (parameter lock) Press "FUNC" again to change the parameter value FUNC Enable to change parameter Press "PROG"...
Page 87
CHANGE maximum frequency limit from 120HZ to 90HZ. Setting Display Description sequence indicator Enter function mode FUNC Increase the value to 4 Select the second digit Increase the value to 1 Press "FUNC" again to change the Maximum FUNC frequency limit Select the second digit Decrease the value to 90HZ Press "PROG"...
8. DISPLAY ERROR CODES A. Inverter self-checking errors Internal protection Noise protection. Self test failure protection Program check sum error EEPROM access error EEP1 EEPROM check-sum error EEP2 Power device failure 1 PF01 Power device failure during acceleration Power device failure 2 PF02 Power device failure during constant frequency...
Page 89
Power device failure 3 PF03 Power device failure during deceleration (stopping) Power device failure 4 PF04 Power device failure during stand-by B. Operation errors Parameter Locked OPE1 To change the contents of CD02~CD52 set CD01=press first PROG FWD or REV only OPE2 Motor direction limiter.
Page 90
Terminal command only OPE4 Accept run command from control terminalonly. Not operation panel. See function description CD12 Over range error OPE5 Operating error message ~ over range. Logic error warning OPE6 Logic error when setting. EXAMPLE : Setting F-min > F-max will result an error. Only changed in standby OPE7 The parameter can only be changed in standby mode.
Page 91
Communication error OPE9 Over heat Over temperature for external indicator. Refer to CD42(FT1) or CD43(FT2). Over load...
9. PRECAUTIONS 9-1 Prior to maintenance, check the following : (1) Before maintenance, be sure to turn the power off and wait until the LED digits vanish in the display. However, approx. 50 VDC still remains immediately after the display disappears, so wait a little bit longer.
10. TROUBLESHOOTING Cause of fault message Display symbol Check point Suggested remedy contents Review the power system. Discharge LED Turned on or Replace No display Check that MCCB has been extinguished MCCB turned on or no poor contact. Increase the acceleration The acceleration time is too short.
11. APPLICATION EXAMPLE 01 : Using rheostart for 2stage speed setting DESCRIPTION : CD12 = 1 ; Terminal command (For External) CD44 = 8 ; 2nd speed singnal enter from FA1 Set FT1 jumper at CF1, see 4-1 description. TERMINAL SPEED SPEED COMMAND ENTRY FREQUENCY KNOB...
Page 95
EXAMPLE 02 : Normal / Jog operation DESCRIPTION : CD00 = Normal speed ; User setting CD04 = Jog speed ; User setting CD12 = 1 ; Terminal command (For External) CD42 = 1 ; Define FT1 Terminal = JOGF function CD43 = 2 ;...
Page 96
EXAMPLE 03 : Auto multi-speed and time programing DESCRIPTION : Speed :CD47=80 (High speed) Speed:CD48=12 (Low speed) Time:CD59=1.25 Time:CD60=0.18 5th SPEED (80HZ) 6th SPEED (12HZ) START STOP 1Hr 25min 18min Value Description Timer disable Speeds with timer for one cycle then stop Speeds with timer for running continually until receive stop command Speeds with timer for one cycle then stop.
13. APPENDIX A. Option braking resistor Part no : E-MSAA-008000 Specification : 60 Ω Remove build-in dynamic brake resistor. Connect a larger capacity resistor, the value should be greater than the table below : Unit : Ohm Model...
C. Remote operator UNIT : M/M A-0000-F306G3 F306 Remote operator E-092A-010200 1 meter extension cable E-092A-030200 3 meter extension cable E-092A-050200 5 meter extension cable...
D. MS4 EMC optional parts Use EMI Filter and clip core to reduce EMC effects. Dimension Fig 1 50.5±0.3 φ 7.5±0.3 Fig 2 A 25.50± 1.00mm B 23.50± 1.00mm C 10.0± 0.30mm D 33.00± 1.00mm Fig 3 A 25.50± 1.00mm B 23.50±...
Page 106
INSTRUCTION MANUAL PART NO : E-PHAA-EMSA09 Model : MS series SEP. 2012 edition ADLEEPOWER SERVICE OFFICE FREQUNCY INVERTER MOTOR DRIVES Guang Dong (China) Taiwan Tel No : 86-757-26656498 Tel No : 886-4-25622651 Fax No : 86-757-26658515 Fax No : 886-4-25628289 E-mail : webmaster@adlee.com...