Installation
1
Ensure the mounting surface is strong enough to handle 3 times the total weight of all the components. Add plywood or other
reinforcing material as necessary to strengthen the surface.
2
Attach the wall bracket. Center the mounting holes on the wall studs. Use all 6 mounting screws to secure the bracket.
3
Lift the inverter so that the inverter bracket is above the wall bracket.
4
Lower the inverter so that the inverter bracket slips into the wall bracket.
5
If GSLC is not used: Secure the inverter to the surface using a minimum of 1 wall screw (or appropriate hardware).
If GSLC is used: Unscrew the inverter bottom screws approximately ¼" (0.6 cm) to 3/16" (0.5 cm).
6
7
Align the GSLC along the bottom of the inverter. Slide the bottom screws into the keyhole slots.
8
Mark the spots for the GSLC mounting feet. (If necessary, remove the GSLC to install wall anchors.) Install screws to secure the feet.
9
Follow the appropriate instructions for installing other components. Different mounting locations are available.
0.5" (1.3 cm)
0.5" (1.3 cm)
16" (40.6 cm)
13.7"
(34.8 cm)
(71.1 cm)
ON/OFF
+ -
INV
RELAY
12V
Switch
Remote
Battery
AUX
AUX
INV
Temp
When
stacking
multiple
inverters:
45.0"
For GSLC door
(114.3
clearance, space
cm)
systems 0.9"
N
N
N
L1 L2
L1 L2
L1 L2
E
E
E
OUT
GEN
GRID
U
U
U
(3.2 cm) apart.
The Radian allows two locations
for the MATE3 mounting bracket
(FW-MB3).
The Radian has one
mounting location for the
HUB product. The GSLC
also has one location.
900-0162-01-00 Rev A.vsd\Page-2\2014-01-24
©2014 OutBack Power Technologies. All Rights Reserved.
8.75"
(22 cm)
Wall Stud
Wall Board
Plywood
(Optional)
Inverter
Bracket
3
Wall
Bracket
28.0"
29.1"
(74.0 cm)
4
Right Side:
Left Side:
The FLEXmax charge
controller is mounted
with the FW-CCB bracket.
The FW-CCB2 allows two
controllers side by side (using
the forward holes to allow for
conduit.)
The Radian has two sets of
9
bracket positions. The GSLC
has one set.
NOTE: The FLEXmax
Extreme charge controller
attaches directly to the wall,
not the Radian system.
It does not use
OutBack brackets.
Wall
16" (40.6 cm)
Stud
1
Plywood (Optional)
4.1"
2
(10.4 cm)
Wall Bracket
Wall Board
6.0"
(15.2 cm)
(20.3 cm)
AC Wire Sizes and Torque Values
Wire Size
AWG
mm
#14 to #10
2.5 to 6
6
#8
10
5
#6 to #4
16 to 25
#3
35
#2
35
#1
50
Bottom
1/0
70
Screws
Keyhole Slots
OutBack recommends that conductors be
7
#6 AWG THHN copper, or larger, rated to 75°C
(minimum) unless local code requires otherwise.
Minimum DC Cable based on
the DC Circuit Breaker
Circuit
Cable Size
Breaker
60
#6 AWG (16 mm
14.0"
80
#4 AWG (25 mm
(35.6 cm)
125
1/0 (70 mm
175
2/0 (70 mm
250
4/0 (120 mm
12.0"
8
(31.8 cm)
Circuit Breaker
Stud
M8
¼ - 20
5/16 - 18
3/8 - 16
Positive Battery Cable Connections
4
Bolt 3/8"
DC Disconnect
Stud
Battery
Positive
Flat
FM80
(+) Lug
Washer
Positive (+)
DC
Terminal
Positive
(+) Plate
19
Flat
Lock
FN-DC
Washer
Washer
Positive (+)
Sense
Nut
Terminal
GSLC175-PV-120/240
GSLC175PV1-120/240
Wall
Stud
GS8048A
5.0"
MATE3
(12.7 cm)
8.0"
9
ON/OFF
INV
RELAY
+ -
Switch
Remote
Battery
AUX
12V
INV
Temp
AUX
9
10
Torque
In-lb
Nm
2
1
20
2.3
25
2.8
N
N
N
L1 L2
L1 L2
L1 L2
E
E
E
U
OUT
U
GEN
GRID
U
35
4.0
35
4.0
40
4.5
HUB
50
5.6
10.3
50
5.6
9
3
7
20
20
18
Torque
11
13
In-lb
Nm
5
2
)
35
4.0
6
2
)
35
4.0
12
14
2
)
50
5.6
2
)
225
25.4
2
)
225
25.4
GSLC175-PV-120/240
Torque Requirements
Torque
Torque
DC Plates
In-lb
Nm
In-lb
Nm
20
2.3
Upper holes (+)
60
60
6.8
35
4.0
Lower holes (+)
50
5.6
50
5.6
Shunt Bolts (–)
6.8
60
and GS-SBUS
225
25.4
Negative Battery Cable
CAUTION:
!
Connections
Equipment Damage
Battery
When connecting cables
Positive
(+) Lug
from the Radian inverter
Flat
to the battery terminals,
Washer
DC
Negative (-)
make sure to observe
Plate
the proper polarity.
(GS-SBUS)
Flat
Connecting the cables
Washer
22
incorrectly can damage
Lock
Washer
or destroy the equipment
Shunt
Nut
and void the product
20
warranty.
RADIAN Series
1
AC Terminals - Inverter
2
DC Terminals - Inverter
3
AC Circuit Breakers
4
DC Circuit Breakers
5
GFDI
6
PV Circuit Breakers
7
Mechanical Interlock (Bypass)
8
Charge Controller Terminals
9
Communication Ports
Auxiliary Terminals
10
11
AC OUT Bus Bar L1
12
AC OUT Bus Bar L2
13
GRID IN Bus Bar L1
14
GRID IN Bus Bar L2
15
GEN IN Bus Bar L1
16
GEN IN Bus Bar L2
17
AC Neutral
18
Ground
19
DC Positive (+) Plate (not used
on GSLC175PV1-120/240)
20
PV Negative (–) Terminals
21
PV Positive (+) Bus Bars
22
DC Negative (–) Plate (GS-SBUS)
2
2
20
22
4
19
15
8
8
21
9
9
17
16
21
10
10
FM80 #1
FM80 #2
FN-DC
FN-DC LED Indicators
Color
Battery State of Charge
> 90% (blinks if charge parameters
Green
are met)
≥ 80%
Yellow
≥ 70%
Yellow
≥ 60%
Yellow
≥ 60% off, < 60% solid, < 50% blinks
Red
FN-DC wiring is displayed
on the Wiring page.
Bolt 3/8"
Wiring to AC terminals is
1
Battery
displayed on the Wiring page.
Lock
Negative
Washer
(–) Lug
N
N
N
L1 L2
L1 L2
L1 L2
E
E
E
OUT
GEN
GRID
U
U
U
Need help?