Setup With Pactware; Connect The Pc; Parameter Adjustment - Vega VEGAPULS 63 Operating Instructions Manual

Radar sensor for continuous level measurement of liquids two-wire 4...20 ma/hart
Hide thumbs Also See for VEGAPULS 63:
Table of Contents

Advertisement

7 Setup with PACTware

Via the interface adapter
directly on the sensor
Via the interface adapter
and HART
Prerequisites
60
7
Setup with PACTware
7.1

Connect the PC

Fig. 34: Connection of the PC directly to the sensor via the interface adapter
1
USB cable to the PC
2
Interface adapter VEGACONNECT
3
Sensor
1
Fig. 35: Connecting the PC via HART to the signal cable
1
Sensor
2 HART resistance 250 Ω (optional depending on evaluation)
3
Connection cable with 2 mm pins and terminals
4
Processing system/PLC/Voltage supply
5
Interface adapter, for example VEGACONNECT 4
Note:
With power supply units with integrated HART resistance (internal
resistance approx. 250 Ω), an additional external resistance is not
necessary. This applies, e.g. to the VEGA instruments VEGATRENN
149A, VEGAMET 381, VEGAMET 391. Common Ex separators are
also usually equipped with a sufficient current limiting resistance. In
such cases, the interface converter can be connected parallel to the
4 ... 20 mA cable (dashed line in the previous illustration).
7.2

Parameter adjustment

For parameter adjustment of the instrument via a Windows PC, the
configuration software PACTware and a suitable instrument driver
2
4
2
3
VEGAPULS 63 • Two-wire 4 ... 20 mA/HART
1