6 Set up with the display and adjustment module
Setup - Current output
Min./Max.
Setup - Lock adjustment
Display - Language
50
The default setting is output characteristics 4 ... 20 mA, fault mode
< 3.6 mA.
In the menu item "Current output Min./Max.", you determine the reac-
tion of the current output during operation.
The default setting is min. current 3.8 mA and max. current 20.5 mA.
In this menu item, the PIN is activated/deactivated permanently.
Entering a 4-digit PIN protects the sensor data against unauthorized
access and unintentional modifications. If the PIN is activated perma-
nently, it can be deactivated temporarily (i.e. for approx. 60 min.) in
any menu item.
Only the following functions are permitted with activated PIN:
Select menu items and show data
Read data from the sensor into the display and adjustment module
Caution:
When the PIN is active, adjustment via PACTware/DTM as well as
other systems is also blocked.
In delivery status, the PIN is "0000".
This menu item enables the setting of the requested national lan-
guage.
VEGAPULS 63 • Two-wire 4 ... 20 mA/HART