600 A 35 kV Class T-OP II connector assembly installation instructions
only positive tolerance
INSULATION
TAPE MARKER
Figure 5 . Line illustration of bare conductor length
Step 6
Bevel insulation
N
ote:
This step is for ease of installation only and has no
effect on electrical characteristics.
Remove sharp edge of insulation by beveling at 45° angle
●
●
for approximately 1/4" (6 mm). (See Figure 6.)
BEVEL
Figure 6 . Line illustration of insulation bevel
Step 7
Clean insulation
Do not apply solvent directly to cable.
N
ote:
Clean insulation thoroughly with solvent dampened rag,
●
●
wiping from conductor end toward insulation shield.
(Refer to Figure 7 .)
Ensure that all traces of conductive residue are removed.
●
●
WIPE INSULATION
WIPING DIRECTION
Figure 7 . Line illustration of insulation cleaning
Step 8
Lubricate and install cable adapter
Lubricate exposed cable insulation.
●
●
Lubricate inside of cable adapter.
●
●
Slide small end of cable adapter over cable using twisting
●
●
motion until small end is flush with tape marker.
(Refer to Figure 8.)
3
INSTALLATION INSTRUCTIONS MN650051EN May 2017
4 3/8 + 1/4"
(111 mm + 7 mm)
BARE
CONDUCTOR
1/4"
(6 mm)
INSULATION
LUBRICATE INSULATION
TAPE MARKER
Figure 8 . Line illustration of insulation cable adapter
After sliding the cable adapter into position make sure
●
●
that no bulge is present (see Figure 9).
Equipment Damage/Personal Injury . Improperly
positioned cable adapter may result in equipment
damage or personal injury .
Cable
Insulation
Cable
Insulation
Shield
Tape
Marker
Correct Positioning
Figure 9 . Cross sectional view of cable
adapter positioning
CABLE ADAPTER
LUBRICATE
WARNING
Major OD
flared out
bulge
Incorrect Positioning