Power Supply Check From The Powered Input/Output Module (Current Consumption Calculation) - Mitsubishi MELSEC iQ-F series User Manual

Hide thumbs Also See for MELSEC iQ-F series:
Table of Contents

Advertisement

Power supply check from the powered input/output module
(current consumption calculation)
If 5 V DC and 24 V DC power supplies of the CPU module are insufficient and system cannot be extended, add a powered
input/output module.
Check if power can be supplied to extension modules with the power supply capacity of the powered input/output module.
Expansion
CPU module
adapters
Calculate following the procedure below.
1.
Check the power supply capacity of the powered input/output module.
(Page 35 Powered input/output module)
Ex.
Type
Powered input/output module
2.
Check the current consumption of the extension module.
(Page 33 I/O module)
(Page 36 Intelligent function module)
Ex.
Type
Input module
Output module
Simple motion module
Bus conversion module
Analog input
3.
Calculate the total current consumption of each power supply.
Ex.
Power supply type
5 V DC power supply
24 V DC power supply
4 SYSTEM CONFIGURATION
52
4.4 Limitation on Current Consumption
Connector
Input
Output
conversion
module
module
module
Model
FX5-32ER/DS
Model
FX5-16EX/ES
FX5-16EYR/ES
FX5-40SSC-S
FX5-CNV-BUS
FX3U-4AD
Total current consumption
460 mA
210 mA
Powered
Input
Output
input/
module
module
output
module
Power supply from powered input/output module
Power supply capacity
5 V DC power supply
965 mA
Current consumption
5 V DC power supply
100 mA
100 mA
150 mA
110 mA
FX5
Bus
FX3
Intelligent
conversion
Intelligent
module
module
module
24 V DC power supply
310 mA
24 V DC power supply
85 mA
125 mA

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-f fx5uc

Table of Contents