If the ambient temperature exceeds 40, use the extension power supply module at the following current
values within the derating range.
Derating curve
Output current [mA]
1200
800
625
400
2.
Check the current consumption of extension devices.
(Page 33 Extension Module)
Ex.
Type
Output module
Connector conversion module
Simple motion module
Input module
Bus conversion module
Analog input
3.
Calculate the total current consumption of each power supply.
Ex.
Power supply type
5 V DC power supply
24 V DC power supply
4.
Check if expansion to the extension power supply module is permitted.
• 5 V DC power supply
5 V DC
power supply capacity
Extension power
supply module
mA
Ex.
1200 mA
• 24 V DC power supply
24 V DC
power supply capacity
Extension power
supply module
mA
Ex.
625 mA
If the calculation result is a negative value, the current consumption exceeds the power supply capacity of the extension
power supply module.
Reconfigure the system, adding extension power supply modules.
4 SYSTEM CONFIGURATION
54
4.4 Limitation on Current Consumption
5 V DC
24 V DC
Ambient
40
55
temperature []
Model
FX5-C32EYT/D
FX5-CNV-IFC
FX5-40SSC-S
FX5-16EX/ES
FX5-CNV-BUS
FX3U-4AD
Total current consumption
480 mA
200 mA
Current consumption
Total number of
extension devices
-
mA
480 mA
Current consumption
Total number of
extension devices
-
mA
200 mA
Current consumption
5 V DC power supply
120 mA
100 mA
150 mA
110 mA
Calculation result
=
mA
720 mA
Calculation result
=
mA
425 mA
24 V DC power supply
200 mA
0 mA
0 mA

Advertisement