Honeywell WPS Series Quick Start Manual page 41

Wireless pressure sensor
Table of Contents

Advertisement

User Manual for the
WPS Series Wireless Pressure Sensor
2.2
Certifications and Approvals
2.2.1 Sensor
See the product label for applicable approvals and ratings
Approval/Item
CSAcus Intrinsically Safe
CSAcus Explosionproof
CSAcus Nonincendive
FM Approvals Intrinsically Safe
FM Approvals Explosionproof
FM Approvals Nonincendive
KEMA 08 ATEX0062X Intrinsically
Safe Flameproof
KEMA 08 ATEX0074
Non-Sparking
IECEx CSA 09.0001X
Intrinsically Safe Flameproof
Non-Sparking
Process Connections in
Division 2 / Zone 2
Enclosure Type
Class II and III installations and Type 4X/IP66 applications require that all cable and unused entries be sealed with a NRTL (National
Recognized Testing Laboratory) listed cable gland or conduit plug. Cable glands and conduit plugs are not supplied with the prod-
uct.
2.2.2 Provisioning Device
Provisioning the WPS Series Wireless Pressure Sensor is accomplished over the air, using the WDM Interface. A device description
file (.DD), supplied with Sensor, is loaded into the WDM system as part of the provisioning process. Handheld infrared provisioning
devices are not supported.
2.3
Agency Compliance Information
This section contains the Federal Communications Commission (FCC), Industry Canada (IC) and Radio Frequency compliance state-
ments for the Honeywell WPS Series Wireless Pressure Sensor.
, ATTENTION
WPS Series units must be professionally installed in accordance with the requirements specified in the
Agency Compliance Professional Installation Guide.
Ratings/Description
CL I, Div 1, Groups A, B, C, & D; CL II, Div 1, Groups E, F & G; CL III, T4
CL I, Zone 0: Ex ia IIC, T4; CL I, Zone 0: AEx ia IIC, T4
CL I, Div 1, Groups A, B, C, & D; CL II, Div 1, Groups E, F & G; CL III, T4
CL I, Zone 1: Ex d IIC, T4; CL I, Zone 1: AEx d IIC, T4
CL I, Div 2, Groups A, B, C & D; CL II, Div 2, Groups F & G; CL III, Div 2, T4
CL I, Zone 2: Ex nA IIC, T4; CL I, Zone 2: AEx nA IIC, T4
CL I, Div 1, Groups A, B, C, & D; CL II, Div 1, Groups E, F & G; CL III, T4
CL I, Zone 0: AEx ia IIC, T4
CL I, Div 1, Groups A, B, C, & D; CL II, Div 1, Groups E, F & G; CL III, T4
CL I, Zone 1: AEx d IIC, T4
CL I, Div 2, Groups A, B, C & D; CL II, Div 2, Groups F & G; CL III, Div 2, T4
CL I, Zone 2: AEx nA IIC, T4
EX II 1 GD: Ex ia IIB; T4 Ta = 70ºC; Ex tD A20 IP66 T90ºC
EX II 2 GD: Ex d [ia] IIB; T4 Ta = 70ºC; Ex tD A21 IP66 T90ºC
EX II 3 GD: Ex nA [nL] IIC; T4 Ta = 84ºC; Ex tD A22 IP66 T90ºC
Ex ia IIB; T4 Ta = 70ºC; DIP A20 IP66 T90ºC
Ex d [ia] IIB; T4 Ta = 70ºC; DIP A21 IP66 T90ºC
Ex nA [nL] IIC; T4 Ta = 84ºC; DIP A22 IP66 T90ºC
Division 2 / Zone 2 apparatus may only be connected to processes classified as
m
non-hazardous or Division 2 / Zone 2. Connection to hazardous (flammable or
ignition capable) Division 1 / Zone 0, or 1 process is not permitted.
Type 4X, IP 66
50095584