Honeywell WPS Series Quick Start Manual page 24

Wireless pressure sensor
Table of Contents

Advertisement

Quick Start Guide for the
WPS Series Wireless Pressure Sensor
4.3.10 Grounding the Antenna
Follow these guidelines to ground the antenna in accordance with national electrical code instructions.
Step
Action
1
Use No. 10 AWG copper or No. 8 or larger copper-clad steel or bronze wire as ground wires for both mast and lead-in. Securely
clamp the wire to the bottom of the mast.
2
Secure the lead-in wire to a lightning arrestor and mast ground wire to the building with stand-off insulators spaced from 4 feet
(1.2 meters) to 8 feet (1.8 meters) apart.
3
The lightning arrestor must be bonded to earth ground in order to function properly. Due to the small diameter coaxial cables
used with the RP-SMA connectors, the lightning arrestor must be grounded independant of the antennas, using number 10
solid wire. This wire must be connected directly to a solid ground. It may be the same ground as is used for the antenna tower.
4
Refer to the WPS-Series Professional Install Guide for further information about lightning arrestors and their installation.
Drill a hole in the building's wall as close as possible to the equipment to which you will connect the lead-in cable. Use a rubber
grommet or feedthru tube to protect the cable from abrasion.
m CAUTION
There may be wires in the wall. Before drilling check that the area is clear of any obstructions or other hazards.
5
Pull the cable through the hole and form a drip loop on the outside close to where the cable enters the building. The drip loop
should have a radius of at least 12 inches (30 cm).
6
Thoroughly waterproof the lead-in area.
7
Connect the lead-in cable to the
en.
18
Honeywell Sensing and Control
WXP-Series Transmitter.
Tighten cables by hand only; do not use tools or you could overtight-
50095585
ISSUE 1

Advertisement

Table of Contents
loading

Table of Contents