Figure 3. Process Connection - Pipe Fitting
3.1.3 General piping guidelines
When measuring fluids containing suspended solids, install permanent valves at regular intervals to blow-down piping.
Blow-down all lines on new installations with compressed air or steam and flush them with process fluids (where possible) before connect-
ing these lines to the sensor's meter body.
Be sure all the valves in the blow-down lines are closed tight after the initial blow-down procedure and each maintenance procedure after
that.
Mount sensor vertically to assure best accuracy, and to obtain optimum R.F. link performance. Position the spirit balance on pressure con-
nection surface of Sensor body.
3.1.4 Sensor Housing Swiveling
The WPS Series sensor housing will swivel through a 350 degree range to facilitate easy reading of the LCD display. To adjust the swivel
mounting:
1.
Insure that the process connector (threaded fitting) is in its final position and is fully tightened, using a wrench on the hex-nut area
above the threads (do NOT tighten using the sensor body).
2.
Loosen the large nut just below the housing using a 1 3/4" wrench.
3.
Swivel sensor housing as needed.
4.
While holding the sensor body in place, gently tighten the large nut with a 1 3/4" wrench to 7 Nm [5.2 ft-lb].