Initial Panel Programming
HS2016/2032/2064/2128 Initial Programming
Please refer to the panel manual section 'Alternate Communicator Set-up' for details.
1. In panel section [377] 'Communication Variables', subsection [002] 'Communication Delays',
sub-subsection [1] 'Communication Delay', program 060 (seconds).
2. In panel section [382] 'Communicator Option 3' set option [5] ON.
3. In panel sections [300] 'Panel/Receiver Communication Paths', subsections [001] to [004],
program the subsection with 02 to 06.
NOTE: Refer to panel manual for additional information.
4. In panel section [350] 'Communication Formats', program the communication format as: CID
(03) or SIA FSK (04).
5. In panel sections [311] - [318] 'Partition Call Directions', program the call direction options for
the system.
6. In panel section [401] 'DLS/SA Options', set toggle option [2] 'User Enable DLS' to ON in
order to perform panel DLS session through Ethernet.
NOTE: Before leaving the premises, the installer should verify all programmed communications
paths. See programming options section [851][901] to send immediate test transmissions.
Communicator Troubles displayed on a HS2016/2032/2064/2128
The communication trouble is the only trouble that will appear on the keypad Liquid Crystal Dis-
play (LCD) when encountered by a communicator installed in a HS2016/2032/2064/2128. For
more information about the trouble on the communicator module refer to the panel event buffer or
by accessing *2 to view the individual trouble types.
The communicator has 2 on-board LED indicators: a yellow trouble LED and a red network con-
nection status LED.
Yellow Trouble LED
This yellow LED will flash to indicate a trouble on the unit. The number of flashes indicates the
type of trouble. See the table below for the coded flashes and the conditions which will activate the
trouble status LED.
Table 5: Yellow Trouble Status LED
# of
Flashes
2
Panel Supervision Trouble
4
Not Applicable
5
Not Applicable
6
Ethernet Trouble
7
Receiver Not Available Trouble
NOTE: Only the highest priority trouble (2 flashes is the highest priority trouble) is indicated.
When this trouble is restored, the next highest trouble will indicate, if present. This will
continue until all troubles have been cleared (yellow LED is not flashing).
Red Network Connection Status LED
BLINKING: Indicates communications in progress.
I
P
NITIAL
ANEL
Table 4: Communicator Path Programming
Value
02
03
04
C
OMMUNICATOR
Trouble
Internet Alarm Communicator Installation Guide
P
ROGRAMMING
Communication Method
Auto Routing
Ethernet 1
Ethernet 2
S
TATUS
# of
Flashes
8
Receiver Supervision Trouble
9
FTC Trouble
10
Not Applicable
12
Module Configuration Trouble
5
L
EDS
Trouble

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tl280

Table of Contents