Baldor VS1MXS51 Installation & Operating Manual page 36

Ac extreme duty microdrive
Table of Contents

Advertisement

Par
Description
No.
Digital input
P1-08
function select
Stop mode
P1-09
select
Acceleration
P1-10
ramp time
Deceleration
P1-11
ramp time
Energy
P1-12
Optimizer
7-2 Parameter Descriptions
Table 7-1 Basic Parameters Continued
Range
0 to 22
0: Ramp to stop with
power loss ride
through
1: Coast to stop
2: Ramp to stop with
'fast stop' on input
power loss
0.0 to 3000.0
0.0 to 3000.0
0: Disabled
1: Enabled
Units
Default
Defines the function of the
digital inputs depending on the
control mode setting in P1-07.
-
0
See Tables 5-3, 5-4, 5-5 and
5-6 for more information.
0: When the drive enable signal
1: When the enable signal is
-
0
2: When the drive enable signal
Acceleration ramp time from
Seconds
5.0
0 to base speed (P1-03) in
seconds.
Deceleration ramp time
from base speed (P1-03) to
standstill in seconds. When
Seconds
5.0
set to zero, fastest possible
ramp time without trip is
activated.
When enabled, automatically
reduces applied motor voltage
-
0
on light load. Minimum value is
50% of nominal rated voltage
(P1-01).
Explanation
is removed, the drive will
ramp to stop at the rate
set in P1-11. If the mains
supply is lost, the drive will
try to continue running by
reducing the speed of the
load using the load as a
generator.
removed from the drive, the
motor will coast (freewheel)
to stop.
is removed, the drive will
ramp to stop at the rate set
in P1-11. If the mains
supply is lost, the drive will
ramp to stop using the
P2-25 deceleration ramp
time.
MN762S