Flue Options; Top Flue - Up & Out; Top Flue - Vertical; Stanley Flue Fittings - Stanley Cara Installation And Operating Instructions Manual

Gas glass stove
Table of Contents

Advertisement

TOP FLUE - UP & OUT
This type of flue configuration should comply with
the following (see Fig 7):
*
The horizontal flue run can not exceed the
vertical flue rise.
*
Minimum vertical flue rise of 0.5 metres.
*
Maximum vertical flue rise of 14.5 metres.
*
Maximum horizontal flue run of 7.5 metres.

TOP FLUE - VERTICAL

This type of flue configuration should comply with
the following (see Fig 8):
*
Minimum vertical flue rise of 0.5 metres (from
top of unit before bend fitting).
*
Maximum vertical flue rise of 15 metres.
*
Maximum vertical flue rise reduced by 0.25
metres for every 45 degree bend fitted.
*
Length of Vertical flue rise must be twice the
length of Horizontal flue run/offset.

STANLEY FLUE FITTINGS

The table below details the list of Waterford Stanley
Approved Flue Fittings for this stove.
Part Code
Description
34100610/9030 HORIZONTAL FLUE TERMINATION
KIT
34100654
VERTICAL FLUE TERMINATION KIT
37100438/9032 COMBUSTIBLE WALL KIT
34100405
950mm STRAIGHT PIPE
34100404
450mm STRAIGHT PIPE
34100403
250mm STRAIGHT PIPE
34100402
100mm STRAIGHT PIPE
34100441
90 DEGREE BEND
34100421
45 DEGREE BEND
45150169
FLAT ROOF FLASHING KIT
75000006
SLATE ROOF FLASHING KIT
45150173/9019 30-45 DEGREE TILE FLASHING KIT

FLUE OPTIONS

Fig.7
Fig.8
11