Stanley Cara+ Installation And Operating Instructions Manual

Stanley Cara+ Installation And Operating Instructions Manual

Solid fuel high output boiler insert stove

Advertisement

Cara+ Solid Fuel
High Output Boiler
Insert Stove
This appliance is hot while in operation and retains its heat for a long period of time after use.
Children, aged or infirm persons should be supervised at all times and should not be allowed
to touch the hot working surfaces while in use or until the appliance has thoroughly cooled.
When using the stove in situations where children, aged and/or infirm persons are
present a fireguard must be used to prevent accidental contact with the stove. The fireguard
should be manufactured in accordance with BS 8423:2002.
INSTALLATION AND OPERATING INSTRUCTIONS

Advertisement

Table of Contents
loading

Summary of Contents for Stanley Cara+

  • Page 1 Cara+ Solid Fuel High Output Boiler Insert Stove This appliance is hot while in operation and retains its heat for a long period of time after use. Children, aged or infirm persons should be supervised at all times and should not be allowed to touch the hot working surfaces while in use or until the appliance has thoroughly cooled.
  • Page 2: Table Of Contents

    TABLE OF CONTENTS PAGE NO. Insert Stove Installation & Operating Instructions ......General .
  • Page 3 PAGE NO. CO Alarms ............Fire Safety .
  • Page 4: Insert Stove Installation & Operating Instructions

    INSERT STOVE INSTALLATION & OPERATING INSTRUCTIONS Please refer to the current standards, BS EN 15287- NOTE: Please note that it is a legal requirement 1:2007 Design, Installation and Commissioning of under England & Wales Building Regulations that chimneys. BS EN 14336:2004: Heating Systems in the installation of the stove is either carried out Buildings.
  • Page 5: Chimney

    If installation is into an existing chimney then it must Fig 2 be sound and have no cracks or other faults which might allow fumes into the house. Older properties, especially, may have chimney faults or the cross section may be too large i.e. greater than 10” diam- eter.
  • Page 6: Fitting Instructions

    FITTING INSTRUCTIONS ALL FLUE INSTALLATIONS ARE THE RESPONSIBILITY OF THE CUSTOMER. Step 1 Prepare the fireplace area. Ensure the opening is The stove must be conencted from the flue spigot to suitable for fitting of the insert stove opening the chimney/ flue with a suitable flue connection that required, i.e.
  • Page 7: Not Fully Lined Chimney

    Step 9 Step 15 Complete the installation of the flexi liner at the top Bolt the spigot to the stove and re-apply fire cement of the chimney in accordance with the manufactur- to the seals where it may have been disturbed dur- ers instructions.
  • Page 8: Front Removal & Fitting

    Then remove the 4 front fixing screws (see Fig.10) Fig 12 which will allow the front casting and the surround- ing shroud to be removed from the boiler by sliding it to the left to clear the secondary air control rod and then pulling it forward, in some circumstances it may be necessary to unscrew the secondary air contol rod before removing the front.
  • Page 9: Ventilation & Combustion Air Requirements

    Extractor Fan All materials used in the manufacture of air vents should be such that the vent is dimensionally stable, There must not be an extractor fan fitted in the same corrosion resistant, and no provision for closure. room as the stove as this can cause the stove to The effective free area of any vent should be ascer- emit smoke and fumes into the room.
  • Page 10: Clearance To Combustibles

    FLOOR PROTECTION CLEARANCE TO COMBUSTIBLES This appliance must be installed on a solid, level, This appliance must be installed in a recess, the concrete base, a non combustible hearth conform- recess should not contain any combustible materi- ing to current Building Regulations must extend to als.
  • Page 11: Stove Dimensions

    STOVE DIMENSIONS Fig.15 TECHNICAL DATA WOOD MANUFACTURED SMOKELESS FUEL Room Water Total Room Water Total Max Output: (kW) 13.2 16.9 Nominal Output: (kW) 14.8 11.1 Typical refuelling intervals to obtain nominal WOOD outputs: 1.5 hr 1 hr Flue Gas Mass Flow: 8.0g/s 8.0g/s Flue Gas Mass at nominal output:...
  • Page 12: Plumbing

    PLUMBING REGULATIONS There must be no gate valves on this circuit and it must have an expansion pipe exhausting to atmos- The plumbing must be in accordance with all phere. Cylinder and pipe work should be lagged to relevant regulations and practices. It must include a minimise heat loss.
  • Page 13: Injector Tee

    Fig 18 INJECTOR TEE Where the gravity and central heating circuits join together to return to the stove we recommend the use of an injector tee connection, situated as close to the unit as possible. This type of tee encourages a stable flow of water through both circuits and helps to prevent priority being given to the stronger SECONDARY AIR CONTROL - SLIDER...
  • Page 14: Recommended Fuels

    When burning wood the primary air control should 20g and 140g. Other fuels are commercially avail- be closed or open a minimal amount to maintain the able and may give similar results. Wood logs up to fire. 420mm long are suitable. All fuels should be stored under cover and kept as dry as possible prior to use.
  • Page 15: Slow Burning

    fire door and re-set control knob to required setting. Fig.22 Do not operate this appliance with the fire door open. (See Fig.21) When burning wood the requirement to riddle the fire is much less. Do not riddle the fire with the pri- mary air open but fully open the secondary air con- trol instead.
  • Page 16: Important Notes

    Use only replacement parts recommended by Waterford IMPORTANT NOTES Stanley. Using unauthorised parts will invalidate Now that your Solid Fuel stove is installed and no your guarantee and may cause damage or doubt you are looking forward to many comforts it injury.
  • Page 17: Co Alarms

    1. Before lighting the stove, ensure that any build- FIRE SAFETY up in the firebox has been removed and that To provide reasonable fire safety the following the ashpan has been emptied. should be given serious consideration: 2. Open the primary air control by turning it 1.
  • Page 18: Exploded View

    EXPLODED VIEW 24. AIR CONTROL KNOB - U00006AXX FIRE DOOR - B00627AXX 25. HINGE - U00153AXX FRONT CASTING - B00628AXX 26. BOILER PLUG - V00016AXX FRONT CASTING SHROUD - B00632AXX 27. SPIGOT TO DOOR HANDLE - V00021AXX DOOR GLASS CLIP - F00003AXX 28.
  • Page 19: Fault Finding

    SYMPTOM POSSIBLE CAUSES REMEDY Stove Difficult To Light Air controls set incorrectly Air controls must be set to maximum settings on initial light-up Moisture content of fuel too high Ensure fuel is sufficiently dry Fire Burns Too Quickly Air controls set incorrectly Adjust Air controls Rope seals perished/worn Replace rope seals...
  • Page 20 Moisture content of fuel too high Use seasoned wood logs Leak in boiler Replace the boiler Manufactured by Waterford Stanley Ltd., Unit 401-403, IDA Industrial Estate, Cork Road, Waterford, Ireland. Tel: (051) 302300 Fax (051) 302315 www.waterfordstanley.com www.stanleystoves.com...

Table of Contents